___________________________________________________________________________________________
ATS-34
11
3.8 Line By Line Programming Table
LINE
DESCRIPTION
VALUE
FACTORY
SETTING
1
Is this ATS operating in 1 phase or 3 phase?
00
1 Phase
01
3 Phase
01
2
Select Switch ATS type
See drawing on the back of this manual for
guide on different ATS types
00) MCCB BTS type ATS (Single motor)
01) Mot type (MCCB with separate motor)
02) Air circuit breaker type (ACB)
03) Double throw type (Without OFF position)
04) Double throw type (With OFF position)
05) Kutai TS-XXX type ATS
06) Magnetic contactor type ATS (MC)
00
3
Select the lead generator. Gen 1 or Gen 2 or
let the controller select the lead generator &
switch the lead by run time on duty cycle or by
starts & run attempts
00
G1 Leading
01
G2 Leading
02
Alternate lead Gen by run time hours
03
Alternate lead Gen by starts & run attempts
02
4
Do not alternate the gen, but to switch only if
the lead gen fails (00).
Alternate both generators by run time on duty
cycle or by the number of starts & run.
In any position the backup gen will always
pickup the load if the lead gen fails.
*
Do not alternate generators ---Set to
00
* Change lead gen by run time on duty
cycle-Set
01 to 250 Hr
gen run time then
switch.
* Change lead by starts -
01 to 10 starts
after
that switch.
8 Hr
01
5
Time delay load transfer
00
250 sec
10 sec
6
Time delay engine cool-down
00
250 sec
30 sec
7
Time delay ATS in CENTER-OFF position
00
99 sec
5 sec
8
G1 over voltage setting
11
50 ( 110
500V )
25 (250V)
9
G1 under voltage setting
08
47 ( 80
470V )
18 (180V)
10
Time delay if there is a problem with G1
voltage output
00
99
sec
( 00 = Without voltage monitor function )
10 sec
11
G1 over frequency setting
51
75 Hz
65 Hz
12
G1 under frequency setting
40
59 Hz
55 Hz
13
Time delay if there is a problem with G1
frequency output
00
99
sec
( 00 = Without frequency monitor function )
10 sec
14
G2 over voltage setting
11
50 ( 110
500V )
25 (250V)
15
G2 under voltage setting
8
47 ( 80
470V )
18 (180V)
16
Time delay if there is a problem with G2
voltage output
00
99 sec
( 00 = Without voltage monitor function )
10 sec
17
G2 over frequency setting
51
75 Hz
65 Hz
18
G2 under frequency setting
40
59 Hz
55 Hz
19
Time delay if there is a problem with G2
frequency output
00
99 sec
( 00 = Without frequency monitor function )
10 sec
20
Display mode setting
00
Cyclic mode
01
Fix mode
00
21
Do you want to calibrate voltage reading?
00
NO
01
YES
00
22
Accept remote switch transfer operation
(Include emergency stop)
00
NO
01
YES
00
23
KCU-02 module address
00
KCU-02 module restricted
01
99
00
24
KCU-02 module transmission rate
01
115200
04
19200 07
4800
02
57600
05
14400 08
2400
03
38400
06
9600
09
1200
03