19
2-3-11.
450-4000-0 Specification (4000 WATT, 100-120 VAC)
Electrical
Specification
Model No.
Item
Inquire
Inquire
Input
Characteristics
Voltage
24VDC
48VDC
Input Over-Voltage
Protection
33
±
0.5VDC
66
±
1.0VDC
Input Under-Voltage
Protection
21
±
0.5VDC
42
±
1.0VDC
Voltage Range
21~33 VDC
42~66 VDC
No Load Current
<1.9 A @24VDC
<1.0 A @48VDC
Power Saving Mode
<0.2A @24VDC
<0.1A @48VDC
Output
Characteristics
Continuous Output Power
4000 VA(
±
3%)
Maximum output Power
(1Min)
> 4000 VA~4600 VA (100%~115%)
Surge Power (1Sec)
< 8000 VA
Frequency
50 / 60 Hz ± 0.5% (Dip Switch Selectable)
Output Voltage
100 / 110 / 115 / 120 VAC (± 5%)
(Dip Switch Selectable)
Efficiency max.
88%
90%
Short-Circuit Protection
1 Sec Shutdown
Output Waveform
Pure Sine Wave (THD < 5%@ Normal Load)
Signal and
Control
Remote Controller Panel
Unit
CR-8 / CR-16 (optional)
LED Indicator
Red / Orange / Green LED
Dry Contact Terminal
By a relay
Remote Control Terminal
6-port Green terminal (for inverter ON / OFF)
Protection
Input Protection
Over / Under Voltage, Reverse Polarity
(Internal Fuse)
AC Output Protection
Short-Circuit, Overload
Others
Over / Under Temperature Protection
(by Heat sink Tempe80
℃
/-20
℃
)
Environment
Operating Temp.
-20
℃
~40
℃
Storage Temp.
-30
℃
~70
℃
Storage Temp. & Humidity
10 ~95% RH
Safety & EMC
Safety Standards
Certified UL 458
(Only for 115/120VAC)
----
EMC standards
Certified FCC class A
E-mark
----
All manuals and user guides at all-guides.com