background image

®

Preparation for Use

When unpacked, the tester should be inspected for any
visible signs of damage, and the preliminary checks
described in the user manual should be performed to ensure
that it is operating correctly.  If there is any sign of damage,
or if the instrument does not operate correctly, return it to
your nearest supplier.
This instrument is powered by three “C” type batteries.

Checking And Proofing The Tester

Switch the sensitivity to “SELF-TEST”.  The buzzer of the
275HP Hi-Prox should beep and the LEDs should light.
This indicates that the 275HP Hi-Prox is operational.

Verify the working of this unit by selecting 240Vac and place
the dome against a low voltage live conductor or rub the
dome with a cloth or against an item of clothing as this
generates a static DC which triggers the detection of circuit.
The light and beeper should go “on” as if a live wire is being
approached.

Approaching the dome near a
computer screen or a TV screen
(not liquid crystal display type)
should also trigger the tester
while on the 240V selection.

2kV

240Vac

6kV

11kV

22kV

33kV

132kV

275kV

OFF

Self

Test

07

®

Front Panel Layout

OFF
Self-Test
240Vac
2kV
6kV
11kV
22kV
33kV
132kV
275kV
Buzzer
LEDs
Battery Holder

- Turn the pick-up sensor off
- Check if the entire circuitry is working
- 240Vac selection
- 2kVac selection
- 6kVac selection
- 11kVac selection
- 22kVac selection
- 33kVac selection
- 132kVac selection
- 275kVac selection
- High noise level buzzer
- High bright low current LEDs

Buzzer

Rotary Selector

LEDs

Battery Holder

06

Summary of Contents for 500HP

Page 1: ...high voltage KV However the 275 HP 500HP is a non contact tester and it is advised that the tester should never come in to contact with cables KV as this tester is merely a non contact AC proximity t...

Page 2: ...c 2800Vac 5500Vac 8200Vac 15500Vac 5cm 5cm 5cm 5cm 5cm 5cm From a distance of 5cm form the conductor the 275HP can detect 90Vac while on the 240Vac setting From a distance of 5cm it will start to dete...

Page 3: ...m 105cm On the 6kV position the 275HP detect 22000Vac from a distance of 75cm On the previous test while on the 2kV position the 275HP needed only 60cm to detect 22000V So if you suspect the conductor...

Page 4: ...URED 22kVac 22kVac 22kVac 22kVac 22kVac 22kVac o 90 o 90 o 90 o 90 o 90 o 90 3000Vac 4000Vac 6000Vac 11000Vac 22000Vac 33000Vac 1cm 9cm 14cm 25cm 36cm 8 The rotary setting selector is now positioned o...

Page 5: ...en misused altered neglected contaminated or damaged by accident or abnormal conditions of operation or handling KUSAM MECO authorized dealer shall extend this warranty on new and unused products to e...

Page 6: ...er to the user manual 02 Specifications Electrical Detecting Ranges Selection Detects voltage from 240V 2kV 6kV 11kV 22kV 33kV 132kV 275kV Variable from 80V or depending on type of source 250V 500V 10...

Page 7: ...stick Verify the rotary switch setting before measuring Make sure it is on the correct setting for your application Always check that the 275HP Hi Prox is working before and after the test Do not touc...

Page 8: ...ed and indicates the wrong information to the user 09 General Description The 275HP Hi Prox consists of an internal pickup sensor plate a rotary switch as sensitivity selector a sound annunciator high...

Page 9: ...a bunched neutral and earth cable as seen in a flexible cable the distance is reduced to 5 cm 05 Typical Uses Identify and check live cables Check and detect live high voltage cables using extension h...

Page 10: ...nst a low voltage live conductor or rub the dome with a cloth or against an item of clothing as this generates a static DC which triggers the detection of circuit The light and beeper should go on as...

Reviews: