CO2 CONTROL - assembly and operating instructions
-10-
Select the mounting point in such a way that a system warning cannot be ignored before entering the danger area.
Please only use sockets and circuits which are constantly in operation and which cannot be
switched on and off as required!
The PA version provides 4 floating outputs for switching. Pre-alarm, main alarm, operation and fault messages can be forwarded.
CO2 CONTROL PA version
Connection and colour layout of the floating outputs
CO2 CONTROL AM / AM PLUS versions
See
CO2 CONTROL AM / AM PLUS assembly instructions
2.5
Setting the geographic height
On the side of the
warning unit
, there is a rotary switch for setting the location height at which the detection system is installed. Ask the operator the height of
the restaurant above sea level. Check this against the height range given in the table and set the position (0...9) of the switch so that the number on the switch is
above the marking on the housing.
Level
Height [m]
above sea level
0
0 .. 250
1
250 .. 500
2
500 .. 750
3
750 .. 1000
4
1000 .. 1250
5
1250 .. 1500
6
1500 .. 1750
7
1750 .. 2000
8
2000 .. 2250
9
2250 .. 2500
An input voltage for the PA outputs of up to
max. 60 VDC / 125 VAC at max. 0.5 A can be
applied.
white:
Input 24V AC/DC
grey:
Pre-alarm
brown:
Main alarm
green:
Operation
yellow:
Fault
Setting of the
altidude above sea
level according to
the table
After setting the height,
the housing on the rotary
switch must be sealed
with the attached
transparent adhesive film!