CO2 CONTROL - assembly and operating instructions
-19-
Alarm mode
Display
Measure
Pre-alarm
Intermittent
warning sound, red
warning light
flashes
Only enter the hazard area if a second person is
present adjacent to the hazard area. Open all doors
wide open!
1. Shut off all of the gas bottles.
2. Find and fix the leak and/or fault.
Call in the dispensing system service team if
necessary!
3. When the CO
2
content drops below the threshold
value, the alarm will reset automatically.
Fault
Continuous
warning sound,
yellow warning
light lit
These can include:
1. Cable break → The cable must be replaced
2. Device fault → Replace the component
3. Sensor unit fault → Replace the sensor unit
4. When replacing the sensor unit with no
re-initialisation → Initialise the system
5. Heavy smoke → Eliminate the cause; the system
will return to operating mode by itself
6. Severe sudden temperature variations → After a
short time, the system will return to normal
operating mode
Pressing the ALARM OFF key will restart the gas
detection system. If the system fault reoccurs, the
equipment will need to be repaired by the service
team.
7
Warranty
KUNDOxT provides a warranty for technical defects arising from the manufacture of the gas detection system within 24 months following the date of assembly
and commissioning.
The device is designed and certified in accordance with TRSK313, and today in accordance
with DIN 6653-2.
It must not be modified in any way. Any change to the device will void any warranty claims!
The warranty covers the replacement or repair of the device free of charge. Additional costs incurred thereby are not covered.
The warranty is only valid when the card attached to the device is retained by the equipment operator, and the attached postcard has been completed by the
installation service and returned by the owner.
Please ensure that the serial number of the installed device is entered on the postcard.
KUNDOxT guarantees that the system requires no calibration and/or adjustments within 4 full years of operation. After 4 years of operation, a calibration will be
performed at our plant at cost (see 4. Maintenance).
8
Instructions for the prevention of hazards due to CO
2
gas
8.1
Code of conduct
1.
Keep calm!
2.
Acknowledge the audible alarm by pressing the "ALARM OFF" key on the warning unit, and another alarm off switch on the
AM / AM PLUS
version.
3.
Determine which alarm is involved!
Main alarm:
Continuous sound,
Red light lit
Pre-alarm:
Intermittent warning sound
Red light flashes
Malfunction:
Intermittent warning sound
Yellow light flashes
For the
CO2 CONTROL AM / AM PLUS
versions in a CO
2
refrigeration equipment area, please observe the notes in the
CO2 CONTROL AM / AM PLUS installation
sheet
!
When the main alarm is triggered, no further access to the hazard area must be allowed!
To eliminate the hazard, an extraction unit (where available) must be used, or the local
fire brigade must be called.