Operating instructions

 

  

Automatic start/stop system for parallel systems 
for product: KEA 252 PA 

File: BA_KEA 252 PA_EN_Ver 2016-07-01 (replaces version 2014-09-22) 

__________________________________________________________________ 

 
     
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1. 

Use and basic operation 

The KEA 252 PA automatic system is used in systems in which 

several gensets

 are operated in 

parallel

. It can 

be used as a peak load genset, CHP module, for emergency power systems, for pure standalone operation or 
all resulting combinations. It is designed so that genset fields that equipped with this automatic system can be 
easily cascaded. A central controller must take over the activating of any mains and coupling switched and the 
selection of gensets.  
The synchronisation unit, the power and cos φ controller, the load distribution in standalone operation and the 
power failure protection in accordance with 

VDE-AR-N 4105

 and the voltage monitor (from Version 8) according 

to 

E  VDE-AR-N  4120

  during  the  mains  parallel  operation  are  included.  All  functions  and  displays  required  in 

VDE 0108

, including the drag indicator display, are fulfilled by this automatic system. Also, the requirements for 

the control of a diesel motor have been fulfilled in accordance with 

VdS 2100-22

The function of the output relays and the parameters

 can be set with a PC.  

Because the KEA 252 has the same dimensions and fastenings as its predecessor, 

replacement is simple

Four  dedicated  operating  messages  and  four  programmable  operating  displays

  can  be  labelled  by  re-

placeable paper strips and are indicated by LEDs.

  All other alarms and all actual and reference values

 are 

shown on the display. The illuminated display shows two lines with up to 16 characters with a character height 
of 10 mm so that it can be read from a greater distance.  

The parameterisation

 can be carried out via the keys and the display or via 

the serial interface

 (LWL or USB 

– automatic switching) with the parameterisation program 

P

ARA

W

IN

Two 

CAN bus interfaces

 are available for coupling to a 

ZLT

 and to a motor management system. However, the 

protocol for the motor management system must be known and implemented. 
The  automatic  system  can  be  cost-effectively  integrated  in  a  communication  system  (K

UHSE 

T

ELEMON

)  via  the 

public telephone or GSM mains by plugging in a 

modem

Important note! 

The functions for the mains parallel operation deviate in part from the previous model KEA 102 

PA because of compliance with the new VDE regulation. 

 

 

GEN.VOLTAGE [V] 
 231   233   229 

Summary of Contents for KEA 252 PA

Page 1: ...nd displays required in VDE 0108 including the drag indicator display are fulfilled by this automatic system Also the requirements for the control of a diesel motor have been fulfilled in accordance w...

Page 2: ...to the preceding model KEA 102 PA 5 7 Automatic operation 5 7 1 Back synchronisation 5 7 2 Peak load operation 5 8 Test operation 6 9 Basic operation of automatic system 6 9 1 Operation of the display...

Page 3: ...r 13 13 2 11 Monitoring the flows 13 13 2 12 Synchronisation fault 14 13 2 13 Power controller defective 14 13 2 14 Cos controller defective 14 13 2 15 Reverse power 14 13 2 16 Maintenance interval re...

Page 4: ...the unit The connection regulations must be observed 2 The PE N must be connected to the terminal 5 of X403 3 The shields of the analogue signals must only be connected to the earthing screw next to...

Page 5: ...os or other controllers 21 Parameterisation via LWL or USB interface automatic switching or direct via the keys and the display 22 Two CAN bus interfaces 23 Diverse expansion options Modem pressure co...

Page 6: ...hrough forwards and backwards using the and cursor keys Within a group they are read like lines of a text from top to bottom The lines are selected by pressing the cursor buttons down and up If the en...

Page 7: ...isation is described in the service manual The parameters of this group can be changed without a valid ID number Switch on time of the display lighting After pressing any button the background lightin...

Page 8: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 9: ...for monitoring All functions U U f f and the response values of the voltage monitors can be parametrised The un dervoltage display also appears if the measuring voltage is connected with a left rotat...

Page 10: ...tching to OFF from another operating mode a genset operation is immediately ended Previously displayed alarms except fault messages 13 and 14 are deleted as long as the respective alarm contact is sti...

Page 11: ...dynamically determined as a master and ensures the load distribution A deselected relieved genset except for the last one switches off and shuts down after the run on time 12 4 3 Peak load with mains...

Page 12: ...f a switch off alarm occurs the collective switch off alarm is output 13 Alarm messages For contact inputs the respective alarm is triggered with the closing operating current circuit or with the open...

Page 13: ...rect monitoring output a relay can be parameterised at standby current such that the message is passed on with standby current even when in OFF operating mode 13 2 7 Analogue input alarms The analogue...

Page 14: ...rised time the actual value must have been within the dead zone this alarm is issued Optionally the genset can be shut down or a peak load start command can be cancelled for example 13 2 14 Cos contro...

Page 15: ...2 Hz GEN Display of the generator voltage against the neutral conductor in the order L1 L2 and L3 and the generator frequency 6 403 400 398 V L1 2 L2 3 L3 1 G Display of the phase to phase voltages fr...

Page 16: ...indicator synchroscope Display 18 runtime until the next maintenance The operating hours counter until the next maintenance is decremented from a maximum value If the counter reading reaches 000000 an...

Page 17: ...tpoint adjuster or directly to the generator via an analogue signal After suspension of parallel operation the generator voltage is controlled in the parametrised window for the voltage control in sta...

Page 18: ...ogue input 0 20 mA channel 4 for variable power specification in mains parallel operation Battery voltage monitor Input for pick up Three free analogue inputs can be optionally equipped with sub board...

Page 19: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 20: ...___________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen Luh...

Page 21: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 22: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 23: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 24: ..._________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Page 25: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Reviews: