background image

   Operating instructions for KEA 252 PA             

13 / 25

       File: BA_KEA 252 PA_EN_Ver 2016-07-01 

 

______________________________________________________________________________________ 

Alfred Kuhse GmbH 

Telephone: +49 4171-798-0 

[email protected] 

Subject to technical changes 

An der Kleinbahn 39, D-21423 Winsen (Luhe) 

Fax: +49 4171-798-117 

www.kuhse.de 

 

 

13.2. 

Description of the alarms 

13.2.1. 

Engine does not switch off  

If the running message of the motor is still pending after the stop time expires, the Motor does not come to a 
standstill alarm is activated. This indicates that the stop equipment (e.g. burned stopping solenoid, jamming gas 
solenoid valve) of the motor is defective. 

13.2.2. 

False start 

The alarm is activated if the genset has not started at the end of the start program. The automatic system is 
locked for any further automatic start-up. 

13.2.3. 

Motor fault 

The alarm starts up if the motor is already running and is brought to a standstill without a stop command. The 
automatic system is locked at the same time. 

13.2.4. 

Overspeed 

For the overspeed monitoring, either the generator frequency or the frequency of a pick-up is used. If the gener-
ator frequency is used for detecting the overspeed, the 

Generator undervoltage

 alarm 

must

 be parametrised 

as an alarm 

to be switched off

 in order to ensure the protection of the machine, even in the event of generator 

voltage failure 

13.2.5. 

Alarms 13 and 14 

Both these alarms are delayed by 0 to 240 sec. by the signal transmission, i.e. for the alarm contact to issue an 
error, the signal must be pending for a parametrised time. Furthermore, both these alarms are also effective in 
the Off operating mode (Off), but without switching on the horn. This means criteria (such as tank overfilling, 
leakage warning) that must always be signalled can be monitored.  

13.2.6. 

Battery voltage monitor 

On the direct monitoring output, a relay can be parameterised (at standby current) such that the message is 
passed on with standby current even when in O

FF 

operating mode.  

13.2.7. 

Analogue input alarms 

The analogue inputs can be equipped with corresponding modules for adapting to different sensors. A variety of 
sensors (PT100, PT1000, current loops, thermocouples, VDO sensors, MotoMeters for motor temperature and 
oil pressure, etc.) can be connected. For each analogue value, two threshold values can be parametrised, which 
trigger an alarm if the value is exceeded or fallen below. 

13.2.8. 

Generator circuit breaker tripped 

If parametrised, the generator circuit breaker is monitored for self-activated switch-off (e.g. by attached overcur-
rent trigger). The alarm is internally controlled if no generator feedback occurs after the G

ENERATOR IS ON

 

switch-on pulse has expired. 

13.2.9. 

Generator switch-off impeded 

The alarm is given if no generator is off feedback is registered approx. 2 seconds after the switch-off command 
for the generator circuit breaker. The genset includes a repeated start command and switches to generator 
operation or to mains parallel operation for peak load systems. 
If an alarm to be switched off now occurs, the genset is switched of and an additional coupling switch or the 
mains can be switched off by an output to be parametrised so the genset is not operated further due to reverse 
power. 

13.2.10.  Alarms of the voltage monitor 
The frequency and voltage deviations of the busbar and of the generator can be displayed as error messages. 
An alarm does not affect the voltage monitor output. If the Gen. underfrequency alarm, for example,

 

has been 

activated as a warning message but the frequency is back in the window, this message remains. However, the 
generator voltage is recognised as ‘good’ for the control process in the automatic system. 

13.2.11.  Monitoring the flows 
If required, the generator flows can be monitored for overcurrent (e.g. 110%), short-circuit (e.g. 300%), asym-
metric load and thermal overload (bimetallic relay). 

Summary of Contents for KEA 252 PA

Page 1: ...nd displays required in VDE 0108 including the drag indicator display are fulfilled by this automatic system Also the requirements for the control of a diesel motor have been fulfilled in accordance w...

Page 2: ...to the preceding model KEA 102 PA 5 7 Automatic operation 5 7 1 Back synchronisation 5 7 2 Peak load operation 5 8 Test operation 6 9 Basic operation of automatic system 6 9 1 Operation of the display...

Page 3: ...r 13 13 2 11 Monitoring the flows 13 13 2 12 Synchronisation fault 14 13 2 13 Power controller defective 14 13 2 14 Cos controller defective 14 13 2 15 Reverse power 14 13 2 16 Maintenance interval re...

Page 4: ...the unit The connection regulations must be observed 2 The PE N must be connected to the terminal 5 of X403 3 The shields of the analogue signals must only be connected to the earthing screw next to...

Page 5: ...os or other controllers 21 Parameterisation via LWL or USB interface automatic switching or direct via the keys and the display 22 Two CAN bus interfaces 23 Diverse expansion options Modem pressure co...

Page 6: ...hrough forwards and backwards using the and cursor keys Within a group they are read like lines of a text from top to bottom The lines are selected by pressing the cursor buttons down and up If the en...

Page 7: ...isation is described in the service manual The parameters of this group can be changed without a valid ID number Switch on time of the display lighting After pressing any button the background lightin...

Page 8: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 9: ...for monitoring All functions U U f f and the response values of the voltage monitors can be parametrised The un dervoltage display also appears if the measuring voltage is connected with a left rotat...

Page 10: ...tching to OFF from another operating mode a genset operation is immediately ended Previously displayed alarms except fault messages 13 and 14 are deleted as long as the respective alarm contact is sti...

Page 11: ...dynamically determined as a master and ensures the load distribution A deselected relieved genset except for the last one switches off and shuts down after the run on time 12 4 3 Peak load with mains...

Page 12: ...f a switch off alarm occurs the collective switch off alarm is output 13 Alarm messages For contact inputs the respective alarm is triggered with the closing operating current circuit or with the open...

Page 13: ...rect monitoring output a relay can be parameterised at standby current such that the message is passed on with standby current even when in OFF operating mode 13 2 7 Analogue input alarms The analogue...

Page 14: ...rised time the actual value must have been within the dead zone this alarm is issued Optionally the genset can be shut down or a peak load start command can be cancelled for example 13 2 14 Cos contro...

Page 15: ...2 Hz GEN Display of the generator voltage against the neutral conductor in the order L1 L2 and L3 and the generator frequency 6 403 400 398 V L1 2 L2 3 L3 1 G Display of the phase to phase voltages fr...

Page 16: ...indicator synchroscope Display 18 runtime until the next maintenance The operating hours counter until the next maintenance is decremented from a maximum value If the counter reading reaches 000000 an...

Page 17: ...tpoint adjuster or directly to the generator via an analogue signal After suspension of parallel operation the generator voltage is controlled in the parametrised window for the voltage control in sta...

Page 18: ...ogue input 0 20 mA channel 4 for variable power specification in mains parallel operation Battery voltage monitor Input for pick up Three free analogue inputs can be optionally equipped with sub board...

Page 19: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 20: ...___________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen Luh...

Page 21: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 22: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 23: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 24: ..._________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Page 25: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Reviews: