Kuhse KEA 101 NSTR Service Manual Download Page 2

 

        SA101NX3-E                                                      - 2 / 8 -                                                        07-01-25 

 

 

D

ESIGN

 

 

The control unit is incorporate into the front door of the switchboard. The front meets the protection class 
IP 44 when installed. The two rows of LEDs are marked with interchangeable labels. The relay unit is 
mounted on the mounting plate and linked to the control unit in the door with the supplied cable. 
The control unit has an optic fibre or USB interface (selected by a toggle switch) for the connection of a PC. 
The following settings (password protected) and analogue readouts are possible. 

 

P

ARAMETERISATION

 

− 

Mains voltage monitor, 

− 

Generator voltage and current monitor, 

− 

Text input (consumer defined) for the first 19 
alarms and encoding for all alarms, 

− 

Battery monitor, 

− 

Start-stop parameters, 

− 

Speed sensing, 

− 

Mains/generator change-over, 

− 

Relay and output functions, 

− 

Names and limit values for the analogue inputs, 

− 

Frequency control for isolated operation, 

− 

Voltage control for isolated operation, 

− 

General parameters. 

A

NALOGUE 

R

EADOUTS

 

− 

Actual values: 
o Voltages, 
o Currents, 
o  Active and apparent load, 
o Power 

factor, 

o Speed, 
o Battery 

voltage, 

o  Actual values of the four analogue channels. 

− 

Actual status of the digital inputs of the relay unit 
RZ 071-D, 

− 

Actual status of the output relays, 

− 

Timers' status. 

 

C

ONNECTION

 

 

 

− 

Trained experts may only make the connections of the KEA. 

− 

The PE(N) must be connected for security reasons to terminal 5 on the X403. 

− 

The charging device must be switched off before the battery is disconnected.

 

− 

When the supply voltage of the control unit has been switched off, you must wait at least 20 
seconds before applying it again. 

− 

The negative pole of the battery must be grounded at the input terminal of the switchboard. The 
minimum conductor cross-section is 10 mm

2

.

 

− 

The supply voltage can be set to 12 or 24 V DC with a switch on the RZ 071-D. 

− 

The screens of the analogue input wiring must be connected to the earth screws on the KEA cover, 
and must have no connection to any other metal parts. 

− 

All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or 
inductive loads must also be fitted with suppressor elements. The same applies for all relays and 
inductors that are used in the switchboard or controlled externally.

 

 
 

The following signals (if needed) are directly applied to the control unit:  

 

− 

Voltage of mains and generator, 

− 

Current of generator, 

− 

Four analogue sensors, 

− 

Pick-up, 

− 

Two analogue output signals, 

− 

Optical fibre or USB for parameterisation, 

− 

Two CAN bus systems. 

 

Although the control system is protected against reverse polarity, the correct polarity when connecting the 
battery voltage must be strictly observed, as reverse diodes or other electronic parts of the switchboard may 
possibly be damaged. 

 

The fuse on the RZ 071-D will be blown, if the control system is connected 

with the wrong polarity! 

 

Due to the fact that most of the control relays may be configured for various functions, only the status print 
out of the supplied control unit is to be considered as a binding document. It must be observed, that in case of 
a possible replacement of a unit, any modifications made after commissioning cannot be taken into account 
by the manufacturer.  

 

 
 

Changes without further notice reserved.

 

Summary of Contents for KEA 101 NSTR

Page 1: ...connection to any other metal parts The supply voltage can be set to 12 or 24 V DC with a switch on the RZ 071 D When the supply voltage of the control unit has been switched off you must wait at least 20 seconds before applying it again All coils must be fitted with reverse diodes to prevent high voltage peaks All other coils or inductive loads must also be fitted with suppressor elements The sam...

Page 2: ...it has been switched off you must wait at least 20 seconds before applying it again The negative pole of the battery must be grounded at the input terminal of the switchboard The minimum conductor cross section is 10 mm2 The supply voltage can be set to 12 or 24 V DC with a switch on the RZ 071 D The screens of the analogue input wiring must be connected to the earth screws on the KEA cover and mu...

Page 3: ...ied The chosen parameter cannot be deselected now 5 Select the figure or letter of the parameter that you want to modify with the and cursor keys Numerical parameters can be increased or decreased by increments of 1 with the and buttons Press the same buttons to negate parameters that are displayed with a letter signs alarm coding etc 6 Press OFF and ALARM OFF together to store the displayed param...

Page 4: ...at only those functions listed in the Operation manual are actually implemented The PARAWIN parameterisation program also shows only the parameters that are possible for the particular control unit Group Function Section in FUNCTION AND PARAMETERISATION 2 Encoding of alarms Alarm monitoring 3 Mains voltage monitor Voltage monitor 4 Generator voltage monitor Voltage monitor 4 Generator current moni...

Page 5: ...wo programmable modes for this input input always active or input only active along with a mains voltage failure If an active command is stated the start of genset will be initiated and the load will be transferred from mains to generator supply in the operation mode AUTO If the genset is already running in TEST or AUTO mode or was started by the signal REMOTE START WITHOUT LOAD TRANSFER the gener...

Page 6: ... fails To switch off the generator breaker again both signals terminals 18 and 25 must be cut Terminal 26 External command GENERATOR OFF If a command is applied here the generator CB is immediately switched off and remains off as long as the signal is applied Terminal 27 Not used This terminal can be used as an alarm input Terminal 28 Not used This terminal can be used as an alarm input Terminal 2...

Page 7: ...ich can be fitted with interface cards for ο PT 100 PT1000 ο Current loops ο 0 10 V DC ο Thermocouple NiCr Ni ο Temperature and pressure VDO sensor ο Battery charging current Two analogue outputs 0 20 mA or 0 10 V Under development Relay unit RZ 071 D Device for attachment on a mounting rail dimensions depth 300 x 100 x 90 mm Weight approx 0 7 kg can be installed wherever required Protection class...

Page 8: ...400 Volt N 5 230 400 Volt 3 x 400 Volt N 6 3 x 400 Volt 3 x 100 Volt N 7 3 x 400 Volt 230 400 Volt N 8 3 x 400 Volt 3 x 400 Volt N 9 Special voltage or frequency N 0 CT 1 A N 2 CT 5 A N 3 Special voltage or current measurement N 0 Example Control unit for emergency power plants mains and generator voltage 230 400 V current transformer of generator 5 A The order number is 2A101N53 Changes without f...

Reviews: