4 Operation
4.7 Switching Outputs
4.7.7 Changing Display Function of Status LED
The table shows an example with factory settings and with inverted status function for LED3.
The switching points are defined as follows:
= 70 °C,
= 65 °C
= 80 °C,
= 75 °C
Table 8:
Factory settings
Status function
LED3 inverted
Situation
Status
A
Temperature rising to > 70 °C
PNP switching output 3 is closed
OK
LED3 on
LED3 off
B
Temperature rising to > 80 °C
PNP switching output 4 is closed
Error
LED4 and LED3 on
only LED4 on
C
Temperature dropping to < 75 °C
PNP switching output 4 is opened
OK
LED3 on
LED3 off
D
Temperature dropping to < 65 °C
PNP switching output 3 is opened
Error
LED3 off
LED3 on
Here you can invert the status function of LED for a contact: the LED is illuminated if the contact is opened, thus
falls below the minimum temperature, and when the LED is illuminated the status „error“ is indicated. Especially
the recording of incidents depends on the illumination of LED (see chapter 4.9
Diagnostics
, ).
The following menu items are available:
LED = output;
the LED is illuminated if the PNP
switching output is closed.
LED = -output;
the LED is illuminated if the PNP
output is opened.
Please note:
The recording of incidents specifically depends on the illumination of the LED (see
chapter 4.9
Diagnosis
, ).