68
Appendix 1 Specifications
Model
150kVA
250kVA
200kVA
Cabinet capacity
(VA/W)
50k~150k /
50k~150k
50k~250k /
50k~250k
50k~200k /
50k~200k
Module capacity
(VA/W)
50k / 50k
Max. module number
3
5
4
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
138~485Vac
◆
At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆
At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac
Frequency Range
40Hz-70Hz
Power Factor
≥
0.99
Current THDi
≤
3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage: 220V:+25 %( op10%, +15%, +20%);
230V:+20 %( op10%, +15%);
240V:+15 %( op10%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Output
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
1
Voltage Regulation
±1%
Frequency
Utility
Mode
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Battery
Mode
(50/60±0.1)Hz
Crest Factor
3:1
THD
≤
2% with linear load
≤
4% with non linear load
Overload
Inverter overload capability:
◆
105% < load
≤
110%: transfer to bypass mode after 60
min
◆
110% < load
≤
125%: transfer to bypass mode after 10
min
◆
125% < load
≤
150%: transfer to bypass mode after 1
min
Bypass overload capability:
◆
Temperature
≤
30°C, load
≤
135%: run for a long time
◆
Temperature
≤
40°C, load
≤
125%: run for a long time
◆
1000% load: run for 100 ms
Battery
Voltage
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±
288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs
optional)
360Vdc~600Vdc (30~40 pcs, 36 pcs define, 36 and 50 pcs
no power derating; 32~34 pcs output power factor 0.9;30
pcs output power factor 0.8;)