71
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS
immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO
Shut down UPS immediately
Battery
Advanced Battery Management
Noise Suppression
Complies with EN62040-2
Communication Interface
CAN, RS485, RS232, LBS, Parallel, Relay card, SNMP
card(optional)
Environment
Operating
Temperature
0
℃
~
40
℃
Storage
Temperature
-25
℃
~
55
℃
Humidity
0
~
95% non condensing
Altitude
< 1500m
Display
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Status LED
UPS Fault, Alarm and normal
Reading On the
LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage, parameter set,
history record…
Other
UPS cabinet
(without PDU)
(W*D*H)(mm)
485×850×620(Without Caster)/485×850×682(With Caster)
UPS cabinet
(with PDU)
(W*D*H)(mm)
485×850×842(Without Caster)/485×850×904(With Caster)
Module
Dimensions
(W*D*H)(mm)
440*620*130
Cabinet Weight
(Kg)
70-95
105-125
90~110
125~145
100~120
135~155
Module Weight
(Kg)
28
31
34
Safety Conformance
CE,EN/IEC 62040-3,EN/IEC 62040-1-1
Appendix 2 Problems and Solution
In case the UPS cannot work normally, it might be wrong in installation, wiring or operation.
Please check these aspects first. If all these aspects are checked without any problem, please
consult with local agent right away and provide below information.
(
1
)
Product model name and serial number, which can be found in LCD display.
(
2
)
Try to describe the fault with more details, such as LCD display info, LED lights status, etc.
Read the user manual carefully, it can help a lot for using this UPS in the right way. Some FAQ
(frequently asked questions) may help you to troubleshoot your problem easily.
No.
Problem
Possible reason
Solution
1
LCD not display
The network cable is not
fixed properly or the
telephone line of the front
door is not fixed properly.
Connect the network cable and
telephone cable properly.
2
LCD Blue screen
LCD is Interference
Take out the cable and insert back
properly
Summary of Contents for HPM3300E
Page 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Page 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Page 43: ...42 ...
Page 48: ...47 ...
Page 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...