WIKA Operating Instructions Level Transmitter
– BLM-SF-FM
4.2.2.10 Using the PV simulation mode
For diagnostics purpose of the connected process control system, it is
possible to simulate an arbitrary measurement value without moving the
float physically. Hereby, external switching functions and cabling can be
tested.
Access:
Setup -> 4-20 mA -> PrimVar -> Simulation
Possible values:
-
100 … (SL+100) mm
4.2.2.11 Mapping of the analogue output to a measurement channel
It is possible to use any measurement channel of the sensor for control of
the analogue output.
This channel is designated “PV” (Primary Value). By
means of the HART® protocol, all channels can be read out at any time.
Access: Setup -> HART -> PrimVar -> Mapping
Possible settings are:
Variable Channel Value
Units (short)
PV
0 Level
m
(*)
, mm, cm, ft, in
SV
1 Interface
m
(*)
, mm, cm, ft, in
TV
2 Electronics temperature
°C
(*)
, °F, °r, K
QV
3 Signal-to-Noise ratio
dB
4 Percent PV **)
%
5 Analogue current **)
mA
6 Filling volume
m3
(*)
, gl, l, ig, br, bs, y3, f3, i3, lb
7 Percent filling volume
%
8 Filling mass
kg
(*)
, g, t, p, st, lt, ou
244 Percent PV **)
%
245 Analogue current **)
mA
246 PV **)
247 SV **)
248 QV **)
249 TV **)
(*): Standard setting
**): Not available as PV