9.1
Typical installation positions
Examples
Special features
Horizontal installation, direction of flow from
bottom to top.
4)
Horizontal installation, direction of flow from top to
bottom.
4)
Horizontal installation (for example under the
ceiling)
Vertical installation.
4)
Twin pumps must not be arranged in 'direction of flow from top to bottom', since
under certain operating conditions the changeover flap will not shut off completely,
which might produce reverse flow in the second pump. In this case, changeover from
the first to the second pump might cause damage.
4)
Condensation water holes O = open, X = closed