4.5 Configuration and function
1
2
3
5
4
Fig. 3: Illustration of Surpress Feu SFE.2
1
Control unit
2
Control cabinet
3
Pump
4
Manifold
5
Baseplate
The fully automatic pressure booster system pumps the fluid to the consumer
installations in the set pressure range with a non-self-priming single-stage centrifugal
pump.
The system is controlled and monitored by a micro-processor control unit (1). The
duty pump is started up when the pressure falls below the set start-up pressure and
stopped when the stop pressure (start-up pr delta p) is reached. The pumps
are automatically started up in a different order for each new cycle to equally
distribute the pump operating hours. A minimum run time of 180 seconds is factory-
set for each pump in order to limit the frequency of pump starts. The operating
status is displayed via LEDs.
The fire-fighting system is factory-set to the values listed in the following table:
Table 5: Settings
Connection types
Description
pstop
[bar]
Delta p
[bar]
pstart
[bar]
Pinl
[bar]
C & A
SFE.3 32-20
2,5
0,8
1,7
0
SFE.3 32-30
3,5
0,8
2,7
0
SFE.3 32-40
4,3
0,8
3,5
0
SFE.3 32-50
5,5
0,3
5,2
0
SFE.3 32-60
6,8
0,8
6,0
0
SFE.3 32-75
8,2
0,8
7,4
0
SFE.3 40-15
2,3
0,8
1,5
0
SFE.3 40-25
3,1
0,8
2,3
0
SFE.3 40-30
3,9
0,8
3,1
0
SFE.3 40-35
4,7
1,5
3,2
0
SFE.3 40-45
5,4
1,5
3,9
0
SFE.3 40-50
6,1
1,5
4,6
0
SFE.3 40-60
7,4
1,5
5,9
0
V
SFE.3 32-20
4,0
0,8
3,2
1,5
SFE.3 32-30
5,0
0,8
4,2
1,5
SFE.3 32-40
5,8
0,8
5,0
1,5
SFE.3 32-50
7,0
0,3
6,7
1,5
SFE.3 32-60
8,3
0,8
7,5
1,5
SFE.3 32-75
9,7
0,8
8,9
1,5
SFE.3 40-15
3,8
0,8
3,0
1,5
SFE.3 40-25
4,6
0,8
3,8
1,5
SFE.3 40-30
5,4
0,8
4,6
1,5
SFE.3 40-35
6,2
1,5
4,7
1,5
SFE.3 40-45
6,9
1,5
5,4
1,5
SFE.3 40-50
7,6
1,5
6,1
1,5
SFE.3 40-60
8,9
1,5
7,4
1,5
Design
Function
Automatic mode
4 Description
Surpress Feu SFE.3