moviBOOST VP
7.8
Warnings and alerts - overview
18
Alert
Description
Sens. fail discharge
Failure pressure transmitter
discharge side (value under 4
mA). Replace PT and reset
system.
System pressure too
System pressure too long under
low
minimum value (3-5-13).
System pressure too
System pressure too long above
high
maximum value (3-5-11).
No water available
Insufficient water or pressure at
suction side.
Thermal failure
Thermal failure urgent
Thermal supply valve
Thermal failure supply (current
too high).
Level sensor fail
Failure level sensor in receiver
tank (value under 4 mA). Replace
l.s. and reset system.
Fire alarm
Alert when “external ON”
contactor opens
Warning
Description
Maintenance required
Customer service required
Thermal fail Pump 1
Thermal failure pump 1
(temperature too high).
Thermal fail Pump 2
Thermal failure pump 2
(temperature too high).
Thermal fail Pump 3
Thermal failure pump 3
(temperature too high).
Thermal fail Pump 4
Thermal failure pump 4
(temperature too high).
Thermal fail Pump 5
Thermal failure pump 5
(temperature too high).
Thermal fail Pump 6
Thermal failure pump 6
(temperature too high).
Pump 1 out of service
Pump 1 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
Pump 2 out of service
Pump 2 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
Pump 3 out of service
Pump 3 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
Warning
Description
Pump 4 out of service
Pump 4 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
Pump 5 out of service
Pump 5 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
Pump 6 out of service
Pump 6 set to manual OFF via
parameter 1-2-1. Deactivate by
selecting automatic mode.
High water level
Water level in receiver tank too
high.
Critical water level
Water level in receiver tank
critical (almost empty).
Water level too low
Water level in receiver tank too
low (system shut down for dry
running protection).
Spurious data
Receiving unfamiliar data from
variable frequency drive.
Serial framing
Communication to variable
frequency drive is “framing”
Serial parity
Communication with variable
frequency drive is “parity”
Serial timeout
Communication to variable
frequency drive is “timeout”
Unrequested message
Receiving unrequested message
from variable frequency drive
Buffer overrun
Receiving “log buffer overrun”
message from variable frequency
drive
Failure FC1
General failure variable frequency
drive 1
Failure FC2
General failure variable frequency
drive 2
Failure FC3
General failure variable frequency
drive 3
Failure FC4
General failure variable frequency
drive 4
Failure FC5
General failure variable frequency
drive 5
Failure FC6
General failure variable frequency
drive 6
24 V out of range
Internal 24 V supply out of range
Analog 5V out of ran
Internal 5 V supply out of range
3 V out of range
Internal 3 V supply out of range
External OFF
Warning when opening the
“external OFF” contactor
Summary of Contents for moviBOOST VP
Page 1: ......
Page 12: ...moviBOOST VP 7 5 2 Menu structure Main menu KSB logo actual value display 10 ...
Page 14: ...moviBOOST VP 7 7 Parameter list 12 ...
Page 15: ...moviBOOST VP 13 ...
Page 16: ...moviBOOST VP 14 ...
Page 17: ...moviBOOST VP 15 ...
Page 18: ...moviBOOST VP 16 ...
Page 19: ...moviBOOST VP 17 ...
Page 23: ...moviBOOST VP 21 15 Electrical performance data ...
Page 24: ...moviBOOST VP 16 Shutoff head 22 ...
Page 29: ...moviBOOST VP NOTES ...
Page 30: ......