moviBOOST VP
7.5.2.1 Access levels
Various access levels have been defined to prevent accidental
or unauthorised access to moviBOOST parameters.
Access levels :
Standard
Unless users log on to one of these access levels, they will
only have limited access to parameters.
Customer
Access level for expert users. This level enables access to all
the parameters required for commissioning.
You have to enter a password under 3-2-1-1 Login. You can
change your password under 3-2-6-4 customer password after
you have entered 7353 (factory password). If you deactivate
password protection via parameter 3-2-6-5, this access level
becomes the standard access level. This is the case with
factory settings.
Service
Access level for service technicians.
Your have to enter a password under 3-2-6-2 Login.
Factory
Access level for the manufacturer only.
Note :
If no keys are pressed for ten minutes, the system
automatically returns to the standard access level.
7.5.2.2 Displaying and changing parameters
The parameter numbers contain the navigation path, which
helps you find a particular parameter quickly and easily. The
first digit of the parameter number indicates the first menu
level, which can be called up directly via the four function
keys.
1-Operation
2-Diagnosis
3-Settings
4-Information
Subsequent steps are carried out via the navigation keys.
Example : Parameter 3-5-1 Setpoint
First, enter the customer password as described under 7.5.2.1
Access levels - customer. Then change the setpoint as
follows :
First digit of parameter number : 3-5-1
Press the third function key for Settings.
3-1
appears on the top left of the screen.
Second digit of parameter number : 3-5-1
Change the display
3-1
on the screen (top left) to
3-5
by pressing the navigation keys.
The confirm the selection, press OK.
3-5-1
appears on the top left of the screen.
You have reached the required parameter.
To change this parameter, press OK again.
Number can then be entered
digit by digit from left to right.
Increase value
Reduce value
The bar above the entry displays the value currently being
entered in relation to the value range.
To confirm the selected value, press OK. The cursor
moves to the next position (second position from
the left).
Make the settings as described above for the subsequent
positions and then
save the new parameter value by pressing OK.
Press ESC repeatedly to return to the main display.
The new setpoint is now active.
7.6
Monitoring
All monitoring and protective functions trigger warnings or
alerts. These are signalled by the amber or red LEDs and
connected to the relay outputs.
All active messages can be displayed in the
Diagnosis
menu under
2-1-1
and acknowledged
individually if the cause of the fault is gone or has
been remedied.
The history of messages can be accessed in the
menu
Diagnosis
under
2-1-2
. This indicates the
start and end of a fault.
You can acknowledge the list of fault messages in
the menu
Diagnosis
under
2-1-3
and clear the
history in the menu
Diagnosis
under
2-1-4
. For this
step, you will have to login at the “Service” level.
When the unit is reset (by switching it on and off
with the master switch), all alerts are reset too.
Resetting alerts may cause the unit to restart automatically.
11
Summary of Contents for moviBOOST VP
Page 1: ......
Page 12: ...moviBOOST VP 7 5 2 Menu structure Main menu KSB logo actual value display 10 ...
Page 14: ...moviBOOST VP 7 7 Parameter list 12 ...
Page 15: ...moviBOOST VP 13 ...
Page 16: ...moviBOOST VP 14 ...
Page 17: ...moviBOOST VP 15 ...
Page 18: ...moviBOOST VP 16 ...
Page 19: ...moviBOOST VP 17 ...
Page 23: ...moviBOOST VP 21 15 Electrical performance data ...
Page 24: ...moviBOOST VP 16 Shutoff head 22 ...
Page 29: ...moviBOOST VP NOTES ...
Page 30: ......