10 Related Documents
KSB Delta Macro
77
of
92
1983.843/04-EN
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-7-1-4-1
Additional tank filling
Disabled
Disabled
Everybody
Service
-
Enabled
2-7-1-4-2
Inlet valve type
Tank filling additional solenoid valve
Additional tank-
filling solenoid
valve
Everybody
Service
-
Tank filling proportional valve
2-7-1-4-3
Minimum opening angle of
valve
0 … 100 %
0,1
Everybody
Service
-
2-7-1-4-4
Step width for valve actuation
0 … 100 %
0,1
Everybody
Service
-
2-7-1-5
Drinking water protection
-
-
-
-
-
2-7-1-5-1
Drinking water protection
Disabled
Enabled
Everybody
Service
-
Enabled
2-7-1-5-2
Maximum time between usage
of drinking water
0… 31 d
168 h
Everybody
Service
-
2-7-1-5-3
Response
Message only
0: Message only
Everybody
Service
-
Message and flushing of inlet line
2-7-1-5-4
Time for flushing drinking water
supply
0 … 600 s
10 s
Everybody
Service
-
2-7-1-5-5
Overflow if high-water level is
exceeded
Not allowed
Allowed without
message
Everybody
Service
-
Allowed with message
Allowed without message
2-7-2
Rainwater
-
-
-
-
-
2-7-2-1
Rainwater filling
-
-
-
-
-
2-7-2-1-1
Rainwater filling
Disabled
Disabled
Everybody
Service
-
Enabled
2-7-2-2
Rainwater pumps
-
-
Everybody
Nobody
-
2-7-2-2-1
Source for dry running
protection of rainwater pump
No function
None
Everybody
Service
-
Float switch at rainwater tank
2-7-2-2-3
Delay time for stop
0 … 99 s
1 s
Everybody
Service
-
2-7-2-2-4
Delay time reset
0 … 99 s
1 s
Everybody
Service
-
2-7-2-2-5
Number of rainwater pumps
1 … 2
0
Everybody
Service
-
2-7-2-2-8
Maximum runtime
0 … 3600 s
60 s
Everybody
Service
-
2-7-2-2-9
Changeover delay
0 …. 60 s
1 s
Everybody
Service
-
2-7-2-2-10
Maximum number of pump
starts per hour
1/h … 20/h
20/h
Everybody
Service
-