Position detection by inductive proximity detectors -- Boxes ref. R 1172--K3.... or R 1172--J7....
Technical characteritics of detectors
Box ref. R 1172--J7....
Box ref. R 1172--K3...
Manufacturer:
IFM Effector
Pepperl & Fuchs
Type:
NS 5002
NJ2--V3--N
Conformity certificate:
PTB 01 ATEX 2191
PTB 00 ATEX 2032 X
Nominal voltage:
8.2 VDC
8 VDC
Voltage:
5 to 25 VDC
----------
Off state ondulation:
< 5%
----------
Cable max. resistance:
50
----------
Output activation:
< 1 mA
< 1 mA
Output non activation:
< 2.2 mA
< 3 mA
Self capacity:
< 70
F
< 35
F
Self inductance:
< 190
H
< 50
H
Switching frequency:
800 hz
1000 hz
Resistance to impacts:
< 30g on 10 ms
----------
Resistance to vibrations:
< 10g to 55 hz. a = 1 mm
----------
Protection level:
IP 67
IP 67
Rated operating distance:
2 mm
1,62 mm
Output type:
NF
NF
Connection:
Cable PVC : 2 x 0.14 mm
2
Cable PVC : 2 x 0.14 mm
2
Working temperature
From -- 25
°
C up to + 70
°
C
From -- 25
°
C up to + 70
°
C
Special conditions for safe use
IFM Effector NS--5002
Pepperl & Fuchs NJ2--V3--N
Working ambient temperature :
From -- 10
°
C to + 50
°
C
From -- 10
°
C to + 50
°
C
Max. voltage U
0
:
16 VDC
15,5 VDC
Max. current I
0
:
50 mA
52 mA
Max. Consumption P
0
:
150 mW
169 mW
Hazardous area
Safe area
Wiring diagram
Nc
Nc
Barriers and Interfaces
The barriers and interfaces recommanded by KSB--AMRI can be ordered to any of the manufacturers in the following table. When
ordering, specify that these components are intended for the supply of proximity detectors IFM Effector NS 5002 or Pepperl & Fuchs
NJ2--V3--N.
Manufacturer
Barrier reference
Interface
reference
Laboratory
certificate
Gas group
Permitted
areas
GEORGIN
RDN 11
RDN 211
LCIE 02 ATEX 6104 X
LCIE 02 ATEX 6104 X
II C
II C
Any area
AP 3
NAEV--DI 2 N--A230
LCIE 00 ATEX 6034 X
II C
Any area
AP 3
NAEV--DI 2 N--A115
LCIE 00 ATEX 6034 X
II C
Any other barrier or interface of different construction may be used provided it complies with regulations requirements and that the
calculation and installation rules are respected.
For each reference defined in the above table, KSB--AMRI can supply to the user the corresponding loop calculations.