Ecowatt
®
Drive K120 series
Function parameter list
-96-
Function
code
Name
Description
Default Modify
1: Limit based on A frequency
Thousands place:
0: A+B frequency, ACC/DEC of main reference
A frequency source buffering is invalid
1: A+B frequency, ACC/DEC of main reference
A frequency source buffering is valid, ACC
and DEC are determined by P08.04 (ACC time
4)
P09.14
Low
frequency
proportion
al gain (Kp)
0.00–100.00
1.00
○
P09.15
ACC/DEC
time of PID
command
0.0–1000.0s
0.0s
○
P09.16
PID output
filter time
0.000–10.000s
0.000s
○
P10 group Simple PLC and multi-step speed control
Function
code
Name
Description
Default Modify
P10.00
Simple PLC
mode
0: Stop after running once; the VFD stops
automatically after running for one cycle,
and it can be started only after receiving
running command.
1: Keep running in the final value after
running once. The VFD keeps the running
frequency and direction of the last section
after a single cycle.
2: Cyclic running; the VFD enters the next
cycle after completing one cycle until
receiving stop command and stops.
0
○
P10.01
Simple PLC
memory
selection
0: No memory after power-off
1: Memory after power-off; PLC memories its
running step and frequency before power-off.
0
○
P10.02
Multi-step
speed 0
Setting range of the frequency in 0
th
–15
th
sections are -100.0–100.0%, 100% corresponds
to Max. output frequency P00.03.
0.0%
○
P10.03
Running
time of
0.0s
○