6�6� HEATING LOOPS WITHOUT THE KT-1 OR KT-2A THERMOSTATS
Heating loop
Menu
Parameter name Parameter value range
Note
Heating loop
operational
mode
ON –
Turn on
AUTO –
Working schedule
OFF –
Turn off
ECO loop mode
–10 °C/+10 °C
ECO
lowering the temperature of the heating loop by
the set value.
COMFORT loop
mode
–10 °C /+10 °C
COMFORT
raising the temperature of the heating
loop by the set value.
Setting the
schedule
1–7 days
0–24 h
Weekly operational schedule.
Weather mode
−15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
Heating curve setting at -15°C ambient temperature.
Weather mode
+15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
Heating curve setting at +15°C ambient temperature.
Note
If there is no KT-1/KT-2A thermostat, adaptive regulation is turned off� The KSM regulator calculates the
temperature of the water in the heating loop based on the heating curve with reference temperatures at −15 °C
and +15 °C�
For a constant water temperature in the heating system set the setting at -15°C and at +15°C to the same value�