21
6�4� BUFFER TANK HEATING
Buffer tank
Menu
Parameter name Parameter value range
Note
Buffer tank
operational
mode
ON – Turn on
AUTO – Working schedule
OFF – Turn off
Buffer tank ECO
mode
–10 °C/ +10 °C
ECO
lowering the temperature by the set value.
Buffer tank
COMFORT
mode
–10 °C/ +10 °C
COMFORT
raising the temperature by the set value.
Setting the
schedule
1–7 days
0–4 h
Weekly operational schedule.
Weather mode
−15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
Heating curve setting at -15°C ambient temperature.
Weather mode
+15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
Heating curve setting at +15°C ambient temperature.
Note
If adaptive regulation is turned off, the KSM regulator calculates the temperature of the water in the buffer tank
based on the heating curve with reference temperatures at −15 °C and +15 °C�
For heating at a constant temperature (regardless of ambient outside temperature) set both parameters of the
heating curve at −15 °C and+15 °C to the same value�
Operating instructions
ADAPT System
17-19-45-6702-02