5 Connecting to power supply
OPTISOUND 3030 C • Foundation Fieldbus
51118-EN-210701
but the protective effect against high frequency interference signals
remains.
The total capacitance of the cable and of all capacitors must not
exceed 10 nF in Ex applications.
Take note of the corresponding installation regulations for Ex applica-
tions. In particular, make sure that no potential equalisation currents
flow over the cable screen. In case of grounding on both sides this
can be achieved by the use of a capacitor or a separate potential
equalisation.
5.2 Connection procedure
Proceed as follows:
1. Unscrew the housing lid
2. If a display and adjustment module is installed, remove it by turn-
ing it to the left
3. Loosen compression nut of the cable gland and remove blind
plug
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry
6. Lift the opening levers of the terminals with a screwdriver (see
following illustration)
7. Insert the wire ends into the open terminals according to the wir-
ing plan
Fig. 15: Connection steps 6 and 7
8. Press down the opening levers of the terminals, you will hear the
terminal spring closing
9. Check the hold of the wires in the terminals by lightly pulling on
them
Summary of Contents for OPTISOUND 3030 C
Page 1: ...OPTISOUND 3030 C Handbook Ultrasonic Level Transmitter Foundation Fieldbus ...
Page 3: ...3 Contents OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 Editing status 2019 03 12 ...
Page 50: ...50 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...
Page 51: ...51 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...