GB-6
D
GB
F
NL
I
E
Replacing the solenoid actuator
▷
We recommend replacing the entire actuator set
when replacing the solenoid actuator.
▷
The actuator set is available separately as a
spare part.
Disconnect the system from the electrical power
supply.
Shut off the gas supply.
VG 6 – 5/0
N
2
≤
1,5 x p
u max
4
5
7
8
3
6
10
9
11
When the solenoid actuator is removed, the gas-
filled space in VG 6 – 15/10 is opened. Therefore,
check for internal tightness once the new actua-
tor has been installed, see page 5 (Tightness
test).
Tightness OK: release the gas supply.
VG 0/5 – 65..N
To be able to remove the solenoid actuator,
loosen the hexagonal nut/cap on the solenoid
actuator.
-
N LV1
+
4
10
5
9
6
8
7
Slide the
O-ring
approx.
10 mm up.
= N (-)
blue
= LV1 (+)
black
Screw the solenoid actuator into place.
Release the gas supply.
VG..L
+
N
2
≤
1,5 x p
u max
+
-
N LV1
+
V
15
17
4
3
6
5
14
19
18
20
16
7
8
9
10
11
12
13
Slide the
O-ring
approx.
10 mm up.
= N (-)
blue
= LV1 (+)
black