GB-4
D
GB
F
NL
I
E
VG 6K for compression fittings
▷
The double-cone olive and cap screw are en-
closed.
ø 8 mm
Oel
1
3
4
2
Wiring
WARNING
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is discon-
nected from the power supply.
▷
The solenoid actuator heats up during operation
depending on ambient temperature and voltage.
+90 °C
▷
Use temperature-resistant cable (> 80°C/176°F).
▷
Wiring to EN 60204-1.
Disconnect the system from the electrical power
supply.
Shut off the gas supply.
VG 6 – 5/0
To set the solenoid actuator to the correct posi-
tion, loosen both Allen screws with a 3 mm Allen
key until the solenoid actuator can be turned.
2
1
5
6
4
7
8
9
10
VG with socket
2
1
5
6
4
7
8
9
10
= N (-)
blue
= LV1 (+)
black
Set the solenoid actuator to the correct position
again and screw into place.
VG..N
To set the solenoid actuator to the correct posi-
tion, loosen the hexagonal nut/cap on the sole-
noid actuator until the solenoid actuator can be
turned to the correct position.
-
N LV1
+
5
6
4
8
7
VG..L
Set the solenoid actuator to the correct position.
-
N LV1
+
5
6
4
8
7
VG..N, VG..L
-
N LV1
+
5
6
4
8
7
N (-)
= blue
LV (+)
=
black
9
Set the solenoid actuator to the correct position.
VG..N: screw the solenoid actuator into place.