TC 1, TC 2, TC 3 · Edition 07.22
EN-10
10 MAIntenAnCe
TC 1, TC 2, TC 3 requires little servicing.
We recommend that a function check is carried out
once per year, or at least twice a year if biogas is used.
11 teCHnICAL DAtA
11.1 Ambient conditions
Icing, condensation and dew in and on the unit are
not permitted.
Avoid direct sunlight or radiation from red-hot surfaces
on the unit. Note the maximum medium and ambient
temperatures!
Avoid corrosive influences, e.g. salty ambient air or SO
2
.
The unit may only be stored/installed in enclosed
rooms/buildings.
The unit is suitable for a maximum installation height
of 2000 m AMSL.
Ambient temperature: -20 to +60°C (-4 to +140°F),
no condensation permitted.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
Storage temperature = transport temperature: -20
to +40°C (-4 to +104°F).
Enclosure: IP 65.
This unit is not suitable for cleaning with a high-pressure
cleaner and/or cleaning products.
11.2 Mechanical data
Gas types: natural gas, LPG (gaseous), biogas (max.
0.1 %-by-vol. H
2
S) or clean air. The gas must be
clean and dry in all temperature conditions and must
not contain condensate.
Medium temperature = ambient temperature.
Inlet pressure p
u
: 10 to 500 mbar (3.9 to 195 "WC).
Measurement time t
M
: 5 to 30 s, adjustable. Set at
the factory to 30 s.
Valve opening time: 3 s.
Housing made of impact-resistant plastic.
Connectors: aluminium.
Weight:
TC 1V: 215 g (0.47 lbs),
TC 2 with adapter: 260 g (0.57 lbs),
TC 3: 420 g (0.92 lbs).
11.3 electrical data
Mains voltage and control voltage:
120 V AC, -15/+10%, 50/60 Hz,
230 V AC, -15/+10%, 50/60 Hz,
24 V DC, ±20%.
Power consumption (all LEDs green):
5.5 W at 120 V AC and 230 V AC,
2 W at 24 V DC,
TC 3: plus 8 VA for an auxiliary valve.
Fine-wire fuse:
5 A, slow-acting, H, 250 V, pursuant to IEC 60127-
2/5,
F1: protection of valve outputs (terminals 15 and 16),
fault signal (terminal 12) and supply of the control
inputs (terminals 2, 7 and 8).
F2: protection of safety interlock/controller enable
signal (terminal 6).
The input current at terminal 1 must not exceed 5 A.
Max. load current (terminal 6) for safety interlock/
controller enable and valve outputs (terminals 15
and 16):
at 230/120 V AC mains voltage, max. 3 A resistive
load;
at 24 V DC mains voltage, max. 5 A resistive load.
Fault signal (terminal 12):
fault output at 120 V AC/230 V AC/24 V DC mains
and control voltage:
max. 5 A,
fault output at 120 V AC/230 V AC mains voltage,
24 V DC control voltage:
max. 100 mA.
TC switching cycles:
250,000 pursuant to EN 13611.
Reset: using a button on the device or by remote reset.
Length of connection cable:
at 230 V AC/120 V AC: any, at 24 V DC (supply
connected to PE): max. 10 m permitted,
at 24 V DC (supply not connected to PE): any.
5 cable glands:
M16 x 1.5.
Electrical connection:
Cable cross-section: min. 0.75 mm
2
(AWG 19),
max. 2.5 mm
2
(AWG 14).
12 DesIGneD LIFetIMe
This information on the designed lifetime is based on
using the product in accordance with these operat-
ing instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611 for TC 1, TC 2, TC 3:
switching cycles
time (years)
250,000
10
You can find further explanations in the applicable
rules and regulations and on the afecor website (www.
afecor.org).
This procedure applies to heating systems. For ther-
moprocessing equipment, observe local regulations.