background image

GB-7

D

GB

F

NL

I

E

50 mm

3

4

5

 

Tighten the clamping ring with a torque of 30 Nm.

 6 

 Insulate the ceramic tube. 

 7 

 Reinstall the burner, see page 3 (Installation).

Accessories

Gas nozzle

Burner

Gas 

type*

mm 

(inch)

Order No.

ZMI/ZMIC

ZMI..T

ZMI 6

B

0.94 

(0.037)

75455010 75442157

G

0.76 

(0.029)

75455147 75448032

D

1.30 

(0.051)

75455146

ZMI 5

B

1.40 

(0.055)

75455012 75443157

G

1.05 

(0.041)

75455149 75448031

D

1.78 

(0.070)

75455148

ZMIC 8

B

1.40

(0.055)

75455012

G

1.05

(0.041)

75455149

D

1.78

(0.070)

75455148

B

 = Natural gas

 

G

 = LPG

 

D

 =  Coke oven gas, town gas

Ceramic paste

Apply ceramic paste to the screw connections after 

replacing any burner components in order to avoid 
cold-setting.
Order number: 05012009.

Technical data

ZMI

Capacity: 

ZMI 16: 1 to 2 kW (3.8 to 7.6 10

3

 BTU/h), 

ZMI 25: 2.5 to 4 kW (9.5 to 15.1 10

3

 BTU/h)  

(1.5 to 3.3 kW in conjunction with coke oven gas, 
town gas). 
Capacities in kW refer to the lower calorific 
value H

u

 and capacities in BTU/h refer to the upper 

calorific value H

o

.

Gas inlet pressure: 15 to 70 mbar (6 to 27 "WC),
air inlet pressure: 15 to 90 mbar (6 to 35 "WC), 
each depending on the gas type 
(burner pressures – see www.docuthek.com, 

Type of document: Flow rate curve).

Burner length increments: 100 mm (4").
Gas types: natural gas, LPG (gaseous) and coke 
oven gas; other types of gas on request.
For cold air only.
Flame control: with flame rod.
Ignition: direct spark ignition (5 kV ignition trans-
former).
Right-angle terminal boot: interference-sup-
pressed.
Housing: aluminium.
Flame tube: heat-resistant steel.
Max. temperature at the tip of the flame tube: 

< 1000°C (< 1832°F), 
< 900°C (< 1652°F) for lambda < 1.

Storage temperature: -20°C to +40°C.

ZMIC

Capacity: 
2.5 to 4.2 kW (9.5 to 15.9 10

3

 BTU/h). 

Capacities in kW refer to the lower calorific 
value H

u

 and capacities in BTU/h refer to the upper 

calorific value H

o

.

Gas inlet pressure: up to 100 mbar (up to 40 "WC),
air inlet pressure: up to 120 mbar (up to 47 "WC), 
each depending on the gas type 
(burner pressures – see www.docuthek.com, 

Type of document: Flow rate curve).

Burner length increments: 100 mm (4"), 
length increments of the ZMIC 28..K: 50 mm (2").
Gas types: natural gas, LPG (gaseous) and coke 
oven gas; other types of gas on request.

Replace 
 ceramic  tube 
and copper 
ring.

Lubricate retain-
ing piece with 
ceramic paste 
before fitting 
the clamping 
ring.

Summary of Contents for ZMI

Page 1: ...atal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interven...

Page 2: ...ner bracket 6 Flame tube 7 Enclosed documentation operating instructions and flow rate curves Burner size gas type rated capacity Pmax flame tube length connection see type label D 49018 Osnabr ck Ger...

Page 3: ...ressures can be adjusted ZMI Recommended inlet pressures gas up to 80 mbar up to 32 WC air up to 120 mbar up to 47 WC 1 3 2 Remove the transport safety device Burner Size 16 25 ZMI G G1 ZMI T NPT 1 NP...

Page 4: ...rom the power supply For the ionization and ignition cables use un screened high voltage cable FZLSi 1 7 50 to 180 C 58 to 356 F Order No 04250410 or FZLK 1 7 5 to 80 C 23 to 176 F Order No 04250409 W...

Page 5: ...being formed in the furnace chamber An incorrect change of the burner settings may change the gas air ratio and lead to unsafe operating conditions CO is odourless and poisonous 5 Set the pressure reg...

Page 6: ...ZMI 16G 25 mm Burner L2 ZMI 25B 35 mm ZMI 25D 20 mm ZMI 25G 35 mm L2 ZMIC Reconnect the terminal boot Produce a maintenance report ZMIC K replacing the bellows unit 4 3 2 1 Make a mark to show the len...

Page 7: ...sure 15 to 90 mbar 6 to 35 WC each depending on the gas type burner pressures see www docuthek com Type of document Flow rate curve Burner length increments 100 mm 4 Gas types natural gas LPG gaseous...

Page 8: ...cle 1 1 3 1 1 5 1 3 2 1 3 4 1 5 2 1 7 4 1 5 10 Folgende harmonisierte Normen wurden angewandt The following harmonized standards have been applied Lotte B ren Matthias Rieken Sebastian Escher Datum Da...

Page 9: ...GB 9 D GB Certification Eurasian Customs Union The product ZMI ZMIC meets the technical specifi cations of the Eurasian Customs Union...

Reviews: