Ensure that the electrode length does not change.

L

4

5

1

2

3

Spark plug

Dowel pin

Insulators

4

Burner head

5

Electrode tip

 8 

 Remove dirt from electrode and insulators.

 9 

 If the electrode tip or insulators are damaged, 

replace the electrode.

 

Before changing the electrode, measure the 
total length 

L

.

 0 

 Connect the new electrode with the spark plug 

using the dowel pin.

  

  Adjust spark plug and electrode to the measured 

total length 

L

.

  

 Screw the electrode into the burner housing.

  

 Check distance 

L

:

L2

 ZMI

Burner

L2

ZMI 16B

25 mm

ZMI 16D

21 mm

ZMI 16G

25 mm

Burner

L2

ZMI 25B

35 mm

ZMI 25D

20 mm

ZMI 25G

35 mm

L2

 ZMIC

  • 

 Reconnect the terminal boot.

  • 

 Produce a maintenance report.

ZMIC..K: replacing the bellows unit

4

2

6

7

9

8

Make a mark 
to show the 
length for re-
installing.

Secure the bel-
lows unit here 
while unscrew-
ing the bellows 
unit nut.

4

2

6

7

9

8

 0 

  Insulate the ceramic tube and reinstall the burner, 

see page 3 (Installation).

ZMIC: replacing the ceramic tube
  

 Remove the ZMIC  – see page  6 (ZMIC..K: 

replacing the bellows unit).

50 mm

3

4

5

Spray screw 
connec-
tion with 
penetrating oil 
and unscrew 
clamping ring.

Burner

L2

ZMIC 28B 50 mm

ZMIC 28G 50 mm

Thread (R1) 

must be facing 
in the direction 
of the furnace.

The bellows 

unit gasket 
cord must not 
be twisted 
when installing.

Lubricate 
thread with 
ceramic 
paste before 
assembly.

Summary of Contents for ZMI

Page 1: ...atal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interven...

Page 2: ...ner bracket 6 Flame tube 7 Enclosed documentation operating instructions and flow rate curves Burner size gas type rated capacity Pmax flame tube length connection see type label D 49018 Osnabr ck Ger...

Page 3: ...ressures can be adjusted ZMI Recommended inlet pressures gas up to 80 mbar up to 32 WC air up to 120 mbar up to 47 WC 1 3 2 Remove the transport safety device Burner Size 16 25 ZMI G G1 ZMI T NPT 1 NP...

Page 4: ...rom the power supply For the ionization and ignition cables use un screened high voltage cable FZLSi 1 7 50 to 180 C 58 to 356 F Order No 04250410 or FZLK 1 7 5 to 80 C 23 to 176 F Order No 04250409 W...

Page 5: ...being formed in the furnace chamber An incorrect change of the burner settings may change the gas air ratio and lead to unsafe operating conditions CO is odourless and poisonous 5 Set the pressure reg...

Page 6: ...ZMI 16G 25 mm Burner L2 ZMI 25B 35 mm ZMI 25D 20 mm ZMI 25G 35 mm L2 ZMIC Reconnect the terminal boot Produce a maintenance report ZMIC K replacing the bellows unit 4 3 2 1 Make a mark to show the len...

Page 7: ...sure 15 to 90 mbar 6 to 35 WC each depending on the gas type burner pressures see www docuthek com Type of document Flow rate curve Burner length increments 100 mm 4 Gas types natural gas LPG gaseous...

Page 8: ...cle 1 1 3 1 1 5 1 3 2 1 3 4 1 5 2 1 7 4 1 5 10 Folgende harmonisierte Normen wurden angewandt The following harmonized standards have been applied Lotte B ren Matthias Rieken Sebastian Escher Datum Da...

Page 9: ...GB 9 D GB Certification Eurasian Customs Union The product ZMI ZMIC meets the technical specifi cations of the Eurasian Customs Union...

Reviews: