Checking the usage

DG

To monitor rising and falling pressure.

Positive 

pressure

Negative pres-

sure

Differential 

pressure

DG..S

NH

3

, O

2

air

This function is only guaranteed when used within 

the specified limits – see page 4 (Technical data). 

Any other use is considered as non-compliant.

Type code

Code

Description

DG

Gas pressure switch

6 –  500

Max. setting in mbar

S

Positive pressure (NH

3

, O

2

)

G

With gold-plated contacts

 

-3 

-4 

-5 

-6 

-9

Electrical connection  

via screw terminals 

via screw terminals, IP 65 

4-pin plug, without socket 

4-pin plug, with socket 

4-pin plug, with socket, IP 65

K2 

T2 

N

Red/green pilot LED for 24 V DC/AC 

Blue pilot lamp for 230 V AC 

Red/green pilot LED for 230 V AC 

Blue pilot lamp for 120 V AC

A

External adjustment

Part designations

1

2

3

4

 

1

  Upper housing section with cover

2

  Lower housing section

3

  Hand wheel

4

  M16 cable gland

Type label

Max. inlet pressure, mains voltage, ambient tem-
perature, enclosure: see type label.

DG

2
1

3

D-49018 Osnabrück, Germany

Installation

 CAUTION

Please observe the following to ensure that the DG 
is not damaged during installation and operation:

–  As the temperature increases, the diffusion rate 

of NH

3

 through the diaphragm also increases 

which can cause corrosion of the contacts. For 
this reason, query the closed contacts for opening.

–   The medium NH

3

 must not condense as this can 

lead to increased corrosion of the lower section 

(pressure supply can become blocked) and de-
formation of the diaphragm (causing the switching 
point to shift).

–   Continuous operation at high temperatures accel-

erates the ageing of elastomer materials. In places 

where a high thermal capacity is required, thermal 

equipment trips must be installed upstream of 
the DG.

–  Use approved sealing material only.
–  

Check max. ambient temperature  – see 

page 4 (Technical data).

–   Condensation or vapours containing silicone must 

not be allowed to get into the housing. At subzero 
temperatures malfunctions/failures due to icing 
can occur.

–  The service life will be shorter if subject to ozone 

concentrations exceeding 200 μg/m

3

. When in-

stalling outdoors, place the DG in a roofed area 
and protect from direct sunlight (even IP 65 ver-
sion). To avoid condensation, the cover with pres-
sure equalization element can be used.

–   Avoid subjecting the DG to strong or violent vibra-

tions.

 

Installation position as required, preferably with 
vertical diaphragm. Then the switching point p

S

 

corresponds to the scale value SK set on the 
hand wheel. In other installation positions, the 
switching point p

S

 will change and no longer 

correspond to the scale value SK set on the 
hand wheel. Check the switching point.

ps = SK

ps = SK + 0,18 mbar

ps = SK - 0,18 mbar

 

The DG must not be in contact with masonry. 

Minimum clearance 20 mm.

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Shut off the medium supply.

 3 

 Ensure that the pipeline is clean.

Summary of Contents for DG..S Series

Page 1: ... WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete se...

Page 2: ...orrosion of the lower section pressure supply can become blocked and de formation of the diaphragm causing the switching point to shift Continuous operation at high temperatures accel erates the ageing of elastomer materials In places where a high thermal capacity is required thermal equipment trips must be installed upstream of the DG Use approved sealing material only Check max ambient temperatu...

Page 3: ...ed during operation Note the switching capacity see page 4 Tech nical data 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure Contacts 1 and 3 close when sub ject to falling pressure NO 2 NC 1 COM 3 L1 COM 3 NC 1 NO 2 Adjustment The switching point is adjustable via...

Page 4: ...entire system temporarily 15 minutes 2 bar Switching capacity DG U 24 250 V AC I 0 05 5 A at cos ϕ 1 I 0 05 1 A at cos ϕ 0 6 DG G U 5 250 V AC I 0 01 5 A at cos ϕ 1 I 0 01 1 A at cos ϕ 0 6 DG G U 5 48 V DC I 0 01 1 A Max medium temperature 15 to 80 C Storage and transport temperature 40 to 80 C RoHS compliant pursuant to 2002 95 EC Diaphragm pressure switch silicone free Diaphragm IIR Housing glas...

Reviews: