Tightness test

 1 

 Shut off the downstream pipeline close to the 

valve.

 2 

 Open the valve and the medium supply.

 

Check all used ports for tightness.

N

2

 

900 mbar
max. 2 bar 
< 15 min 

3

4

Maintenance

In order to ensure smooth operation: check the tight-
ness and function of the DG every year.

 

After carrying out the maintenance work, check 

for tightness, see page 4 (Tightness test).

Technical data

Gas type: NH

3

, O

2

 and air.

Max. test pressure for testing the entire system: 
temporarily < 15 minutes 2 bar.
Switching capacity:
DG, U = 24 – 250 V AC: 
I = 0.05 – 5 A at cos 

ϕ

 = 1, 

I = 0.05 – 1 A at cos 

ϕ

 = 0.6.

DG..G, U = 5 – 250 V AC: 
I = 0.01 – 5 A at cos 

ϕ

 = 1, 

I = 0.01 – 1 A at cos 

ϕ

 = 0.6.

DG..G, U = 5 – 48 V DC:  
I = 0.01 – 1 A.

Max. medium temperature: -15 to +80°C.
Storage and transport temperature: -40 to +80°C.
RoHS compliant pursuant to 2002/95/EC.
Diaphragm pressure switch, silicone-free.
Diaphragm: IIR.
Housing: glass fibre reinforced PBT plastic with 
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP 54 or IP 65.
Safety class: 1.
Line entrance: M16 x 1.5, clamping range: diam-
eters of 4 to 10 mm.
Electrical connection type: screw terminals.
Weight: 270 g – 320 g.

Declaration of conformity

We, the manufacturer, hereby declare that the prod-

uct DG..S complies with the essential requirements 
of the following Directive:

– 2006/95/EC

The production is subject to the Quality System pur-

suant to DIN EN ISO 9001:2008, TÜV NORD CERT.
Elster GmbH

Scan of the Declaration of conformity (D, GB) – see  
www.docuthek.com

RoHS compliant

RoHS

2002/95/EC

Contact

Summary of Contents for DG..S Series

Page 1: ... WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete se...

Page 2: ...orrosion of the lower section pressure supply can become blocked and de formation of the diaphragm causing the switching point to shift Continuous operation at high temperatures accel erates the ageing of elastomer materials In places where a high thermal capacity is required thermal equipment trips must be installed upstream of the DG Use approved sealing material only Check max ambient temperatu...

Page 3: ...ed during operation Note the switching capacity see page 4 Tech nical data 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure Contacts 1 and 3 close when sub ject to falling pressure NO 2 NC 1 COM 3 L1 COM 3 NC 1 NO 2 Adjustment The switching point is adjustable via...

Page 4: ...entire system temporarily 15 minutes 2 bar Switching capacity DG U 24 250 V AC I 0 05 5 A at cos ϕ 1 I 0 05 1 A at cos ϕ 0 6 DG G U 5 250 V AC I 0 01 5 A at cos ϕ 1 I 0 01 1 A at cos ϕ 0 6 DG G U 5 48 V DC I 0 01 1 A Max medium temperature 15 to 80 C Storage and transport temperature 40 to 80 C RoHS compliant pursuant to 2002 95 EC Diaphragm pressure switch silicone free Diaphragm IIR Housing glas...