Tightness test
1
Shut off the downstream pipeline close to the
valve.
2
Open the valve and the medium supply.
▷
Check all used ports for tightness.
N
2
900 mbar
max. 2 bar
< 15 min
3
4
Maintenance
In order to ensure smooth operation: check the tight-
ness and function of the DG every year.
▷
After carrying out the maintenance work, check
for tightness, see page 4 (Tightness test).
Technical data
Gas type: NH
3
, O
2
and air.
Max. test pressure for testing the entire system:
temporarily < 15 minutes 2 bar.
Switching capacity:
DG, U = 24 – 250 V AC:
I = 0.05 – 5 A at cos
ϕ
= 1,
I = 0.05 – 1 A at cos
ϕ
= 0.6.
DG..G, U = 5 – 250 V AC:
I = 0.01 – 5 A at cos
ϕ
= 1,
I = 0.01 – 1 A at cos
ϕ
= 0.6.
DG..G, U = 5 – 48 V DC:
I = 0.01 – 1 A.
Max. medium temperature: -15 to +80°C.
Storage and transport temperature: -40 to +80°C.
RoHS compliant pursuant to 2002/95/EC.
Diaphragm pressure switch, silicone-free.
Diaphragm: IIR.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP 54 or IP 65.
Safety class: 1.
Line entrance: M16 x 1.5, clamping range: diam-
eters of 4 to 10 mm.
Electrical connection type: screw terminals.
Weight: 270 g – 320 g.
Declaration of conformity
We, the manufacturer, hereby declare that the prod-
uct DG..S complies with the essential requirements
of the following Directive:
– 2006/95/EC
The production is subject to the Quality System pur-
suant to DIN EN ISO 9001:2008, TÜV NORD CERT.
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
RoHS compliant
RoHS
2002/95/EC
Contact