20
Fct. 3.2.3 TOT ON/OFF
TOT. ON/OFF
Select option
TOT. ON
to start/restart totalizer and select option
TOT.OFF
to stop totalizer. Stopping totalizer means flow will not be
accumulated till the time totalizer is turned on again.
Fct. 3.3.0 APPLICAT.
This submenu groups functions which allow you to view/enter the
application data. These functions give the following information to the
instrument.
– process medium
– operating and normalised density values
– amplifier gain
Fct.3.3.1 FLUID
fluid type
Select whether process medium is steam or gas or liquid.
•
GAS/ STEAM
•
LIQUID
Fct. 3.3.2 DENS. OPR.
density at operating P&T Enter the density of
medium at operating pressure and temperature conditions. The value can be
entered in one of the following units –
•
Kg/m3
•
Kg /Litre
•
Lb/F
• Lb/cft3
LIMITS - 0.05 TO 2000Kg/m
Fct. 3.3.3 DENS. NORM
density at normal P&T
Enter the density of medium at normal pressure and temp conditions. The
value can be entered in one of the following units –
•
Kg /m3
•
Kg
/
Litre
•
Lb/ft
• Lb/cft3
LIMITS – 0.05 to 2000Kg/m 3
Fct. 3.3.4 GAIN
Gain Setting
The gain of the preamplifier can be changed to change the sensitivity of the
meter. The values that can be selected are
•
1
•
5
•
11
•
23
The factory set value is 5 for
LIQUID
and 11 for
GAS
/
STEAM
6.2. Functional order description.21
6.2.1 Physical units
FLOW RATE UNITS
Refer to functions-
Fct 1.1.2 MAX. FLOW
maximum flow rate
Fct. 1.1.3 MIN. FLOW
minimum flow rate
Fct. 1.2.1 FLOW UNITS
for display
Units for flow rate-
for volumetric flow-
•
m3/hr
•
m3/min
•
m3/Sec
•
Litre/hr
•
Litre/min
•
Litre/Sec
•
ft
3
/hr
•
ft
3
/min
•
ft
3
/Sec
•
cft/hr
•
cft/min
•
cft/Sec
•
cuft/hr
•
cuft/min
•
cuft/Sec
•
US GAL/hr
•
US GAL/min
•
US GAL/Sec
•
UK GAL/hr
•
UK GAL/min
•
UK GAL/Sec
•
%
MAX FLOW
(only for
Fct 1.2.1 FLOWUNITS
)
for normalized volumetric flow-
•
Norm.m3/hr
•
Norm.m3/min
•
Norm.m3/Sec
•
Norm,L/hr
•
Norm,L/min
•
Norm,L/Sec
•
Sft3/hr
•
Sft3/min
•
Sft3/Sec
•
Scft/hr
•
Scft/min
•
Scft/Sec
•
%
MAX FLOW
(only for
Fct 1.2.1 FLOWUNITS
)
for mass flow
•
Kg/hr
•
Kg/min
•
Kg/Sec
•
T/hr
•
T/min
•
T/Sec
•
Lb/hr
•
Lb/min
•
Lb/Sec
•
%
MAX FLOW
(only for
Fct 1.2.1 FLOWUNITS
)
TOTALIZER UNITS
Refer to functions-
Fct. 1.2.2 TOTAL.UNITS
totalizer unit for display
units for totalizer-
•
M3
•
Litre
•
ft3
•
cft
•
cuft
•
US Gal
•
UK Gal
VELOCITY UNITS
Refer to functions-
Fct. 1.2.3 VELO.UNITS
velocity unit for display
Units for velocity-
•
m.sec
•
ft/Sec
PULSE OUTPUT UNITS
Refer to functions-
Fct. 1.2.3 RANGE P
Pulse output range value
Units for
RANGE P-
For volumetric flow -
•
PULSE/m3
•
PULS/Litre
•
PULS/Ft3
•
PULS/cFt
•
PULS/cuFt
•
PULS/US Gal
•
PULS/UK.Gal
for normalized volumetric flow -
•
PULS/Norm.m3
•
PULS/Norm.L
•
PULS/Sft3
•
PULS/Scft
for mass flow-
•
PULS/KG
•
PULS/T
•
PULS/Lb
DENSITY UNITS
Refer to functions-
Fct. 3.3.2 DENS.OPR.
Density at operating
P&T
Fct. 3.3.3 DENS.NORM.
density at normal
P&T
Units for density-
•
Kg/m3
•
Kg/Litre
•
Lb/ ft3
•
Lb/cft