23
9 Supplement
SU 600 • 4 … 20 mA signal conditioning instrument
30652-EN-150129
9 Supplement
9.1 Technical data
General data
Series
Instrument for mounting into front panel, switching cabi-
net or housing
Weight
400 g (0.882 lbs)
Housing material
plastic ABS/POM
Connection terminals
Ʋ
Type of terminal
Screw terminal
Ʋ
Max. wire cross-section
1.5 mm² (AWG 16)
Voltage supply
Operating voltage
20 … 253 V AC, 50/60 Hz, 20 … 253 V DC
Max. power consumption
12 VA, 4 W
Sensor input
Number of sensors
1 x 4 … 20 mA
Type of input (switchable)
Ʋ
mode active
Sensor supply through SU 600
Ʋ
mode passive
Sensor has an own power supply
Measured value transmission
4 … 20 mA
Deviation
Ʋ
Accuracy
±20 µA (0.1 % of 20 mA)
Terminal voltage mode active
30 … 22 V at 4 … 20 mA
Current limitation mode active
30 mA
Internal resistance mode passive
< 250 Ω
Detection line break
≤ 3.6 mA
Detection shortcircuit
≥ 21 mA
Adjustment range
Ʋ
Empty adjustment
3.8 … 20.2 mA
Ʋ
Full adjustment
4.1 … 20.5 mA
Ʋ
min. adjustment delta
300 µA
Connection cable to the sensor
two-wire standard cable (screening recommended)
Relay outputs
Quantity
2 x operating relay, 1 x fail safe relay
Contact
Floating spdt
Contact material
AG NI 0.15 hard gold-plated
Switching voltage
min. 10 mV DC, max. 250 V AC/DC
Switching current
min. 10 µA DC, max. 3 A AC, 1 A DC
Summary of Contents for SU 600
Page 1: ...Operating Instructions SU 600 4 20 mA signal conditioning instrument Document ID 30652...
Page 30: ...30 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Page 31: ...31 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Page 32: ...Subject to change without notice 30652 EN 150129...