12
5 Connecting to power supply
SU 600 • 4 … 20 mA signal conditioning instrument
30652-EN-150129
5.3 Connection procedure
Proceed as follows:
1. Mount SU 600
2. Connect sensor cable to terminal 1 and 2, and where applicable,
connect the screen
3. Connect power supply (switched off) to terminal 5 and 6
4. If necessary, connect fail safe and operating relay as well as cur-
rent output
The electrical connection is finished.
5.4 Wiring plan
+ -
1 2
+ -
3 4
18 17 16 15 1413 1211 10 9 8 7 6 5
N- L1+
on
1
2
1
2
%
1
2
3
7
4
5
6
Fig. 5: Terminal assignment SU 600
1 Measurement data input, optionally available with sensor power supply
2 Current output
3 Fail safe relay
4 Relay 2
5 Relay 1
6 Voltage supply
Overview