I
f the fail safe relay is deenergized
,
the red failure lamp
will light
l
Y
ellow
-
R
elay control lamp
-
T
he yellow relay control lamp reacts depending on the
set mode
(
A
/
B
)
-
I
n general
,
the relay control lamp indicates the
activated
(
energised
)
condition of the relay
-
A
dark relay control lamp means that the relay is
deenergised
(
transistor blocks
)
L
aterally on top
(
covered when mounted
)
there is a
DIL
switch
block with six switches
.
T
he individual switches are assigned
as follows
:
l
1
–
A
/
B
mode
-
A
–
M
ax
.
detection or over
fi
ll protection
-
B
–
M
in
.
detection or dry run detection
l
2
–
S
witch o
ff
delay
(
za
)
l
3
–
S
witch on delay
(
ze
)
l
4
–
I
ntegration time
2
s
l
5
–
I
ntegration time
6
s
l
6
–
I
ntegration time
12
s
W
ith switch
1
you can adjust the mode
(
A
–
over
fi
ll protection
or
B
–
dry run protection
).
W
ith switch
2
and
3
you can adjust the switch o
ff
and
/
or switch
on delay independently
.
I
n the example
(
see previous illustration
),
mode
A
(
max
.
detection of over
fi
ll protection
)
is selected
(
switch
1
).
T
he
switch on delay is activated
(
switch
3
)
and the integration time
is set to
8
seconds
(
switch
4
,
5
and
6
).
W
ith switches
4
,
5
and
6
you can adjust the integration time
.
T
he times of the activated time switches accumulate
.
I
f the
switch on
(
ze
)
and switch o
ff
delay
(
za
)
are switched on
together
,
the adjusted time applies to both delay modes
.
I
nformation
:
K
eep in mind that the integration time of the sensor and signal
conditioning instrument accumulate
.
DIL
switch block
SU
501
E
x
-
S
ignal conditioning instrument
17
S
et up
27953
-
EN
-
050616