background image

KROHNE 

 Process instrumentation and measurement solutions

Flow

Level

Temperature

Pressure

Process Analysis

Services

Head Office KROHNE Messtechnik GmbH
Ludwig-Krohne-Str. 5
47058 Duisburg (Germany)
Tel.: +49 203 301 0
Fax: +49 203 301 10389
[email protected]

© KROHNE 07

/20

16 - 4

00430

7801 -

 MA

 O

P

TI

BRI

D

G

E

 R01

 en -

 Su

bj

ect t

o chan

ge

 wi

th

ou

t no

ti

ce.

The current list of all KROHNE contacts and addresses can be found at:
www.krohne.com

Summary of Contents for OPTIBRIDGE

Page 1: ...USB interface cable for HART devices OPTIBRIDGE OPTIBRIDGE OPTIBRIDGE OPTIBRIDGE Handbook Handbook Handbook Handbook KROHNE 07 2016 4004307801 MA OPTIBRIDGE R01 en ...

Page 2: ... or any part thereof without the prior written authorisation of KROHNE Messtechnik GmbH Subject to change without notice 2 www krohne com 07 2016 4004307801 MA OPTIBRIDGE R01 en Copyright 2016 by KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany IMPRINT ...

Page 3: ...the operator 8 2 Device description 9 2 1 Scope of delivery 9 2 2 Device description 10 2 3 Nameplate 11 3 Installation 13 3 1 General notes on installation 13 3 2 Storage and transport 13 3 3 Electrical data 14 3 4 Pre installation requirements 14 3 5 Installation procedure 15 3 6 Connecting the device 17 4 Start up 19 4 1 Starting up for the first time 19 4 2 Operating the device with PACTwareTM...

Page 4: ... OPTIBRIDGE 6 Service 28 6 1 Availability of services 28 6 2 Returning the device to the manufacturer 28 6 2 1 General information 28 6 2 2 Form for copying to accompany a returned device 29 6 3 Disposal 29 7 Technical data 30 7 1 Technical data 30 7 2 Dimensions 31 ...

Page 5: ...ION In the table below x is a placeholder for possible multi digit alphanumeric combinations depending on the available version Release date Electronic revision Changes and compatibility Documentation 2016 03 01 ER 1 0 X_ MA OPTIBRIDGE R01 CAUTION The device is not approved for operation within the hazardous area Operate the device outside the hazardous area only CAUTION Responsibility for the use...

Page 6: ...ertheless we provide no guarantee that the contents are correct complete or up to date The contents and works in this document are subject to copyright Contributions from third parties are identified as such Reproduction processing dissemination and any type of use beyond what is permitted under copyright requires written authorisation from the respective author and or the manufacturer The manufac...

Page 7: ... 3 Product liability and warranty The operator shall bear responsibility for the suitability of the device for the specific purpose The manufacturer accepts no liability for the consequences of misuse by the operator Improper installation or operation of the devices systems will cause the warranty to be void The respective Standard Terms and Conditions which form the basis for the sales contract s...

Page 8: ...ings must be observed without fail Even partial disregard of this warning can lead to serious health problems and even death There is also the risk of seriously damaging the device or parts of the operator s plant WARNING Disregarding this safety warning even if only in part poses the risk of serious health problems There is also the risk of damaging the device or parts of the operator s plant CAU...

Page 9: ... For further information contact your local sales office INFORMATION Inspect the packaging carefully for damages or signs of rough handling Report damage to the carrier and to the local office of the manufacturer INFORMATION Do a check of the packing list to make sure that you have all the elements given in the order INFORMATION Look at the device nameplate to ensure that the device is delivered a...

Page 10: ...cable connector 5 for sensor with VP2 connector optional Adapter cable M8 Strands for OPTIBRIDGE with M8 connector male 4 and strands 6 optional INFORMATION Look at the device nameplate to ensure that the device is delivered according to your order Figure 2 2 Construction of the device 1 USB 2 0 2 OPTIBRIDGE 3 M8 connector female 4 M8 connector male 5 VP cable connector 6 Strands ...

Page 11: ...1 en 2 3 Nameplate Figure 2 3 Example for a nameplate 1 Manufacturer 2 Device name 3 Order code 4 Serial number 5 Electronic revision ER 6 Manufacturing date Ingress protection 7 Electronic electric device waste marking Observe the operation installation instruction CE marking ER 1 0 0 ...

Page 12: ...1 Manufacturer 2 Device name 3 Order code 4 Serial number 5 Electronic revision ER 6 Approvals 7 Manufacturing date Ingress protection 8 Electronic electric device waste marking Observe the operation and installation instruction INFORMATION Look at the device nameplate to ensure that the device is delivered according to your order ...

Page 13: ... national regulations for electrical installations WARNING During installation of the device make sure that you use ESD electrostatic discharge protection equipment WARNING Observe without fail the local occupational health and safety regulations Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists INFORMATION Inspect the packag...

Page 14: ...n requirements System requirements Windows 7 32 bit 64 bit PACTwareTM 4 1 Administrator rights WARNING Do not lengthened or shorten the cable with M8 connector female The total length of the device included adapter cable must not be longer than 3 m 9 84 ft Use only the adapter cables which are intended for the device INFORMATION The CD contains several software packages DTM drivers etc The softwar...

Page 15: ... subdirectory KROHNE OPTIBRIDGE DTM Start installation of PACTwareTM 4 1 It is recommended to install the ICS Generic HART DTM and HART Communication FDT as well in order to enable you to use generic HART devices for communication with PACTwareTM Start installation of the device DTM WARNING During installation of the device make sure that you use ESD electrostatic discharge protection equipment CA...

Page 16: ...3 INSTALLATION 16 OPTIBRIDGE www krohne com 07 2016 4004307801 MA OPTIBRIDGE R01 en Figure 3 1 Installation procedure ...

Page 17: ...and max 5 Nm WARNING During installation of the device make sure that you use ESD electrostatic discharge protection equipment CAUTION The resistor load for HART communication is already integrated in the OPTIBRDIGE CAUTION Moisture on the sensor connector must be avoided Moisture may cause a short circuit and a malfunction of the sensor If moisture has entered the connector dry it with air e g ho...

Page 18: ... krohne com 07 2016 4004307801 MA OPTIBRIDGE R01 en Connection diagram for any 2 wire HART device Figure 3 3 Connecting with adapter cable M8 strands 1 M8 cable connector male 2 Black Ub 3 White Ub 4 Yellow Green shield S 5 HART slave ...

Page 19: ...reTM 4 1 Add device 1 Connect device 2 INFORMATION To avoid injury and material damage only operate the device under the following conditions Installation and connection in accordance with the manufacturer s instruction Temperature and electrical data in accordance with the technical specifications The equipment parts necessary for safety are effective in the long run never disable them during ope...

Page 20: ... After the installation of the software shown on page 15 the CommDTM is ready for use In order to actually use the CommDTM it is necessary to start the frame application Then the device catalogue of the Frame Application has to be updated The device DTM is now registered and ready for work 5 2 Offline configuration 5 2 1 Driver configuration This window is used to select one of the connected devic...

Page 21: ...preambles for communication with HART bus devices This value is used to establish the initial connection to a HART device The number of preambles to use for communication with the device is read from the device itself and used for communication afterwards Max Retries 3 This parameter specifies how often the HART master retries to transmit information in case of an error Max Scan Address 4 This par...

Page 22: ... and it can be accessed via menu Additional functions Add and select a device DTM and press the button Set Address 2 to access the function Make sure that the device DTM is added but not connected offline INFORMATION To use the following functions the device DTM has to be connected via pressing the connect button in PACTwareTM Figure 5 3 Device list ...

Page 23: ...rame applications New DTM TAG 2 Set a new TAG for the device DTM HART Address 3 This is the address of the device that the device DTM should communicate with This number is the polling address The long address with device and manufacturer ID is acquired from the device when the connection is established If you are not sure about the polling address of your device start the topology scan With this ...

Page 24: ...a pressing the connect button in PACTwareTM Figure 5 5 Device list Address The Polling address of the device State State field is used to display an icon that reflects the state of device configuration The following icons are possible This entry represents a Child DTM This DTM is not associated to any existing HART device This entry represents an existing HART device No Child DTM is configured for...

Page 25: ...utton Stop Scan is activated The scan can be stopped at any time The button Set Address is used to open the window to change the polling address of the selected DTM and or slave device 5 3 2 Changing polling address Select a Device DTM in the window Device List and press the button Set Address to access the window Select a device DTM 1 Click on Set Address 2 button INFORMATION Do not change the po...

Page 26: ...evice via VP connector and no DTM for this slave is added and connected Current address 1 This is the current address of the device on the HART bus The content of this field is set automatically when the window is opened New address 2 This is the desired new address for the device Change address 3 Press this button to transfer the address change Status 4 Information about status of the address cha...

Page 27: ...ge of address itself fails for other reasons an error message is displayed in the status field With the help of this window it is possible to change the address of a HART slave device together with the address of a connected Device DTM This window is opened by the Set Address button in the device list window for list entries that represent devices with assigned DTMs Slave address 1 The new address...

Page 28: ...ion or repair please pay strict attention to the following points Due to statutory regulations on environmental protection and safeguarding the health and safety of the personnel the manufacturer may only handle test and repair returned devices that have been in contact with products without risk to personnel and environment This means that the manufacturer can only service this device if it is ac...

Page 29: ...when it is returned Date Signature Stamp CAUTION Disposal must be carried out in accordance with legislation applicable in your country Separate collection of WEEE Waste Electrical and Electronic Equipment in the European Union Separate collection of WEEE Waste Electrical and Electronic Equipment in the European Union Separate collection of WEEE Waste Electrical and Electronic Equipment in the Eur...

Page 30: ...ctor female Connectors Adapter cable M8 strands M8 connector male strands Operating conditions Ambient temperature 0 55 C 32 131 F Storage temperature 40 70 C 40 158 F Altitude 0 2000 m 6600 ft Relative humidity 5 95 rH not condensing Installation conditions Ingress protection IP65 not for USB 2 0 Weight Approx 400 g 0 88 lbs Materials Housing Stainless steel 1 4301 AISI 304 V2A PP Communication F...

Page 31: ...irements of the EC directives The manufacturer certifies successful testing of the product by applying the CE mark Electromagnetic compatibility EMC Directive 2014 30 EU Ex IECEx Ex ia IIC ATEX II 1 G Ex ia IIC Directive 2014 34 EU Figure 7 1 Dimensions Dimensions mm Dimensions inch a Ø35 Ø1 38 b 300 11 81 c 85 3 35 d 130 5 12 e 1700 66 93 f 300 11 81 g 300 11 81 e f g ...

Page 32: ... Services Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389 info krohne com KROHNE 07 2016 4004307801 MA OPTIBRIDGE R01 en Subject to change without notice The current list of all KROHNE contacts and addresses can be found at www krohne com ...

Reviews: