background image

6/6

Minimum load impedance

A minimum load impedance of 250 

is required to enable the HART signals to be modulated on

the current output. Series-connect an appropriate resistor if the devices located in the current
output circuit should not attain this value. It will then be possible via the minimum load impedance
e.g. to connect the HART communicator or smart converter in parallel without interrupting the
current output. Please note that the load impedance should not exceed a maximum of 500 

.

HART operating tools / DD

The IFC 090 can be operated either via its local operator interface or by means of the HART
communicator or the CONFIG program. Both operating tools are available from KROHNE.
Operator control by means of the HART communicator requires a device description (DD) which
we can load for you into the communicator. We can, of course, also load the DDs of all
manufacturers who have filed their DDs with the HART Communication Foundation. If you wish to
use the IFC 090 in your operating tool, for example, please ask for the description of the HART
command used so that you can address the complete IFC 090 functionality via HART.

In the near future we shall also be supporting the ASM tool from Rosemount and the SIPROM tool
from Siemens.

Power supply units / isolation switching amplifiers

You will need an appropriate power supply unit if the current output is to operate in the passive
mode. Please ensure that this power supply unit is also suitable for HART communication.
This applies equally to isolation switching amplifiers that are sometimes used in the active mode.

Additional functions for HART version

Fct.

Text

Description and settings

3.08

LOCATION

Set any tag name (max. 10 characters)
Characters assignable to each place:

A - Z, a - z, 0 - 9,  or  “ - ” (= blank character)

Press 

key to transfer to  Fct. 3.08 “LOCATION”.

3.09

COM

HART communications-interface

OFF

(switched off)   

}

Select with 

key.

HART (switched on)
Press 

key,

set “ADDRESS” 

with 

and  

→ 

keys,

Range: 001 - 015

Press 

key to transfer to  Fct. 3.09 “COM”.

Summary of Contents for IFC 090 F

Page 1: ...g of the primary head Installation location and connection to power Section 1 Pages 1 1 1 6 Electrical connection of outputs and inputs Section 2 Pages 2 1 2 6 Factory settings and start up Section 3...

Page 2: ...rminals B1 B and B2 B 2 4 2 6 Connection diagrams for outputs and inputs 2 5 2 6 3 Start up 3 1 3 2 3 1 Switch on and measurement 3 1 3 2 Factory settings 3 2 Part B IFC 090 D Signal converter 4 1 5 1...

Page 3: ...8 1 Replacement of power fuses 8 1 8 2 Changeover of operating voltage on AC Versions 1 and 2 8 1 8 3 Turning the display PCB 8 1 8 4 Retrofitting the display unit 8 2 8 5 Power fuses and illustratio...

Page 4: ...nge I Error 1 06 Output or input B1 setting see Fct 3 07 terminal B1 1 07 Output or input B2 setting see Fct 3 07 terminal B2 3 01 Language 3 02 Primary head Meter size GK value Field frequency Power...

Page 5: ...perator Improper installation and operation of the flowmeters systems may lead to loss of warranty In addition the General conditions of sale forming the basis of the purchase contract are applicable...

Page 6: ...ith built in devices from direct sunlight Fit a sunshade if necessary When installed in switchgear cabinets signal converters must be adequately cooled e g use fans or heat exchangers Do not expose si...

Page 7: ...ment of the signal converter For exceptions compact systems refer to installation instructions for the primary head Connection diagrams I and II for power supply and electrical connection between prim...

Page 8: ...t shield 5 Inner sheath 6 Mu metal foil 2nd shield 7 Stranded drain wire 2nd shield 0 5 mm2 or AWG 20 8 Outher sheath Field current cable C with single shielding Cross section is dependent on required...

Page 9: ...grounding instructions are contained in the Ex installation instructions for hazardous duty devices supplied only with such devices The primary head is connected to ground by means of an FE functiona...

Page 10: ...F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 C 302 F Recommended length of signal cable for magnetic field frequency 1 6 power frequency 1 3 4 Cable lengths max distance b...

Page 11: ...tra low voltage with protective separation in conformity with VDE 0100 Part 410 or equivalent national regulations Systems used in hazardous locations are subject to special regulations applying to th...

Page 12: ...S status output C control input 2 2 Current output I The current output is galvanically isolated from all input and output circuits Setting data and functions can note down on page 0 3 Please also re...

Page 13: ...ct 6 2 for operator control The pulse output can be operated in the active or passive mode Active mode The current output is the internal voltage source connection of electronic totalizers EC Passive...

Page 14: ...tor power OFF power ON SIGN I F R mode Forward flow Reverse flow SIGN P F R mode Forward flow Reverse flow TRIP POINT limit switch inactive active AUTO RANGE automatic range change high range low rang...

Page 15: ...current inputs B1 and B2 All operating data and functions can be set Display version IFC 090 D see Sect 4 and 5 19 Fct 1 06 and 1 07 for operator control Basic version IFC 090 B see Sect 6 2 for opera...

Page 16: ...put Pactive for EC Current output Ipassive I I U 15 V DC from current output I 23 mA operation without current output I 03 mA operation with current output U 15 V DC from current output I 23 mA operat...

Page 17: ...ge change BA with F R flow measurement Iactive BA changeover via S2passive B2 F R changeover via S1passive B1 V R BA I I I I V V V R R V R R high range low range 11 U 15 V DC I 03 mA Automatic range c...

Page 18: ...e electronic section shows the measurement status Remove the cover using the special wrench LED flashing green measurement correct everything all right green red momentary overdriving of outputs and o...

Page 19: ...refore it may be necessary to change the factory setting of some or all of the following functions low flow cutoff SMU Fct 1 03 Sect 5 3 current output I Fct 1 05 Sect 5 6 pulse output P Fct 1 06 Sect...

Page 20: ...ta column 3 00 INSTALL 2 00 TEST 1 00 OPERATION 3 05 USER UNIT 3 06 APPLICAT 3 07 HARDWARE 3 04 ENTRY CODE 3 03 ZERO SET 3 02 FLOWMETER 3 01 LANGUAGE 2 02 HARDW INFO 2 01 TEST Q 1 07 OUTPUT B2 INPUT B...

Page 21: ...e I overranging current output I P overranging pulse output P Keys for operator control of signal converter Magnetic sensors to set the converter by means of a handheld bar magnet without opening hous...

Page 22: ...ry Code 1 must now be entered each keystroke acknowledged by To terminate operator control Press key repeatedly until one of the following menus Fct 1 00 OPERATION Fct 2 00 TEST or Fct 3 00 INSTALL is...

Page 23: ...3 9 7 4 5 m 3 h r 3 9 7 3 5 m 3 h r select next text To alter texts units For units the numerical value is converted automatically 3 7 6 9 9 L i t e r S e c Change to number setting To transfer from t...

Page 24: ...scale range for flowrate Q100 Select unit m3 hr Liter Sec US Gal min user unit factory set is Liter hr or US MGal day see Fct 3 05 Press key to transfer to number setting Setting ranges The ranges ar...

Page 25: ...lected transfer to subfunction REV RANGE REV RANGE Set full scale range for reverse flow of Q100 appears only when 2 DIR selected 100 PCT same as forward flow Q100 see Fct 1 01 PERCENT setting range 0...

Page 26: ...M symmetrical pulse duty ratio 1 1 over total range Press key to transfer to subfunction VALUE P VALUE P Set pulse value per unit volume appears only when PULSE VOL set under SELECT P above xxxx PulS...

Page 27: ...e table DN 10 1000 mm equivalent to 3 8 40 inch Select with key Press key to transfer to subfunction FULL SCALE FULL SCALE Full scale range for flow Q100 To set refer to Fct 1 01 FULL SCALE above Pres...

Page 28: ...here 1x 103 or 2 64172x10 4 Factor FM volume per 1m3 Setting range 1 00000 E 9 to 9 99999 E 9 10 9 to 10 9 Press key to transfer to subfunction TEXT TIME TEXT TIME Set text for required time unit max...

Page 29: ...error message deleted automatically TOTALIZER Totalizer has been reset Cancel error message in RESET QUIT menu ADC Analog digital Error message deleted automatically converter overranged after elimin...

Page 30: ...ss twice return to measuring mode QUIT YES Delete error messages ERROR QUIT Error messages deleted Return to measuring mode Reset totalizer s in RESET QUIT menu Key Display Description Measuring mode...

Page 31: ...f YES set under Fct 3 04 ENTRY CODE key in the 9 keystroke CODE 1 now Fct 1 00 OPERATION Fct 1 01 FULL SCALE 4x Fct 1 05 CURRENT I FUNCT I RANGE I If REV RANGE appears here press keys and again 04 20...

Page 32: ...ge flashing number cursor with key Use key to shift cursor 1 place to right Press key to return to Fct 1 01 FULL SCALE Note if VALUE P is displayed after pressing key PULSE VOL is set under Fct 1 06 P...

Page 33: ...ith key Transfer to totalizer unit setting using key m3 cubic metres Liter litres US Gal US gallons user defined unit factory set Liter or US MGal see Sect 5 12 Select with key Transfer to totalizer f...

Page 34: ...Fct 1 04 subfunction DISP FLOW The counting range is dependent upon the meter size and has been selected such that the totalizer will count for a minimum of 1 year without overflow Only part of the t...

Page 35: ...1 01 PERCENT settable range Setting range 005 150 of Q100 see Fct 1 01 Select with key Press key to transfer to number setting Press key to transfer to subfunction RANGE I RANGE I select measuring ra...

Page 36: ...es per unit volume flowrate PULSE TIME pulses per unit time for 100 flowrate Select with key Press key to return to subfunction PULSWIDTH PULSWIDTH select pulse width press key AUTO automatic 50 of th...

Page 37: ...to right or left with key Press key to return to Fct 1 06 PULS B1 or Please refer to Sect 3 2 factory settings VALUE P set pulse value per unit time appears only when PULSE TIME has been set under SEL...

Page 38: ...YYY N C contact XXX YYY Hysteresis difference between XXX and YYY Press key to transfer to number setting 1st digit cursor flashes Change flashing digit cursor with key Use key to shift cursor 1 plac...

Page 39: ...change see also Sect 5 19 setting range 5 80 PERCENT ratio of low to high range 1 20 to 1 1 25 value must be greater than that of Fct 1 03 L F CUTOFF Press key to transfer to number setting 1st digit...

Page 40: ...primary constant GK press key 1 0000 9 9999 note information on instrument nameplate do not change setting Change flashing digit cursor with key Shift cursor 1 place to right or left with key Transfer...

Page 41: ...ey 3 60000 E 3 factory set 3 6 x 103 for hour or 8 64 x 104 for day set factor FT in seconds Setting range 1 00000 E 9 to 9 99999 E 9 10 9 to 10 9 Change flashing place cursor using key Use key to shi...

Page 42: ...f the outputs with SIGN I or SIGN P see Sect 5 8 Current and or pulse output must be set to 2 DIR see Fct 1 05 and 1 06 subfunctions FUNCT I and FUNCT B1 5 15 Characteristic of outputs I Current outpu...

Page 43: ...atus outputs B1 or B2 Define operating mode of output terminals see Sect 5 16 Press key Set status output B1 or B2 to TRIP POINT by pressing key 1 to 9 times Press key to transfer to number setting 1s...

Page 44: ...ENT of Q100 ratio between low and high range 1 20 to 1 1 25 Press key to return to Fct 1 06 or 1 07 status output B1 or B2 External range change by means of control input Fct 1 06 or 1 07 control inpu...

Page 45: ...procating pumps see also Sect 6 4 6 5 and 6 6 Special case applications Press key to return to Fct 3 07 APPLICAT With built in option empty tube identification change to subfunction EMPTY PIPE EMPTY P...

Page 46: ...remove the display unit For this purpose detach the two screws R and fold display unit to the side see illustration in Sect 8 5 3 Insert the RS 232 adapter forming the connection to the PC or laptop i...

Page 47: ...h the two screws R and fold display unit to the side see illustration in Sect 8 5 4 Carefully pull off the blue 9 pin plug X1 X4 forming the connection to the primary head 5 Detach the 2 recessed head...

Page 48: ...display unsteadiness Fct 1 02 TIMECONST change time constant Set to ALL and time t in seconds Recommended t s Example min number of strokes in operation 50 strokes minute t s 20 s With this setting t...

Page 49: ...etting to BARGRAPH to allow better assessment of display unsteadiness Fct 1 02 TIMECONST change time constant Setting to ONLY I to ALL if pulse output too unsteady Set time constant to approx 20 s obs...

Page 50: ...must be set to 1 DIR or 2 DIR IMPORTANT In Menu 1 05 the RANGE I parameter must be set to 4 20 mA or in the case of variable setting the value for I 0 must be at least 4 mA In Menu 3 09 the COM1 param...

Page 51: ...ed their DDs with the HART Communication Foundation If you wish to use the IFC 090 in your operating tool for example please ask for the description of the HART command used so that you can address th...

Page 52: ...s confirm with key STORE NO If new value not to be stored press key 3x 4x return to measuring mode STORE YES Fct 3 03 ZERO SET Store new zero value 2x 3x Measuring mode with new zero Key Display Descr...

Page 53: ...CODES Fct 2 02 HARDW INFO Terminate hardware information 2x 3x Measuring mode Switch off power source before opening the housing Before consulting factory about errors or flow measurement problems ple...

Page 54: ...lashes red green Overranging of A D converter Reduce flowrate if unsuccessful current or pulse output test as described in Sect 7 5 Measuring tube drained Fill measuring tube A D converter overranged...

Page 55: ...talizer not Connection polarity incorrect Connect properly as described counting any pulses in Sect 2 4 2 7 Totalizer or external Check connection cables voltage source defective totalizer and externa...

Page 56: ...tomatically after cause has been eliminated D 4 ADC Analog digital converter Error message deleted overranged automatically after cause has been eliminated D 5 FATAL ERROR Fatal Error Replace signal c...

Page 57: ...illiammeter Test ok check connection cables and receiver instrument replace if necessary Test faulty current output defective Replace signal converter see Sect 8 7 or contact Krohne Service Current ou...

Page 58: ...fective replace signal converter see Sect 8 7 or contact Krohne Service Current output is external Check connection and cables voltage source short circuit see Sect 2 3 2 4 2 7 or current pulse output...

Page 59: ...tus output defective replace signal converter see Sect 8 7 or contact Krohne Service Output terminal B1 or B2 Change setting under not set to status output Fct 3 07 Group D I P S Fault Symptom Caus Re...

Page 60: ...ompletely fill the measuring tube of the flowmeter with the process liquid 7 5 Test of primary head Action Typical result Incorrect result Resistance measurement flowmeter defective at the blue 9 pin...

Page 61: ...tronic frequency counter input resistance approx 1 k range 0 1 kHz time base min 1 second see connection diagrams in Sect 2 6 A a Switch off power source before opening the housing b Unscrew the cover...

Page 62: ...eets condition Y X 4 3 Calculate setpoint reading I for current output I I0 Y I100 I0 in mA X I0 current 0 4mA at 0 flowrate I100 current 20mA at 100 flowrate 4 4 Calculate setpoint reading f for puls...

Page 63: ...onstant V in m3 t in hr K 7074 see Table DN in mm Calculation of X and position of Y X Q100 x K 200 x 7074 61 905 GK x DN2 3 571 x 80 x 80 Y 80 position of switch Y see front panel GS 8A comes closest...

Page 64: ...8 5 for fuse ratings and order numbers 7 Reassemble in reverse order points 5 1 above Switch off power source before opening the housing 1 Unscrew the cover from the terminal compartment using the spe...

Page 65: ...4 and 5 for operator control and display of measured values 7 Grease the thread and gasket of the new housing cover with recess for the display and tighten down using the special wrench Retrofitting t...

Page 66: ...es A special electronic unit is available for hazardous duty flowmeters see separate Ex installation instructions Switch off power source before opening the housing 1 Unscrew the cover from the termin...

Page 67: ...t 8 9 insert the 2 pin plug of the field power cable into plug connector X1 and the 5 pin plug of the signal cable into plug connector X4 Do not kink or twist the cables 11 Secure the display unit wit...

Page 68: ...nnector for connec tion of external add on equipment see Sect 6 2 X3 24 pin socket connector X4 5 pin plug connector Pins 1 5 signal cable see Sect 7 5 and 7 7 X6 10 pin plug connector for dispay unit...

Page 69: ...IFC 090 Spares and accessories Order No Plug for supply power all AC Versions 100 240 V AC 3 31122 02 24 V AC DC Versions 3 31122 03 for outputs inputs 3 31122 01 Display unit retrofit kit for Basic...

Page 70: ...013 26 019 09 033 93 053 02 076 35 0135 8 0212 1 0305 4 0415 6 0542 9 0662 8 0848 2 00000 2121 00000 5429 00001 222 00003 392 00007 634 00013 57 00021 20 00034 74 00054 28 00084 82 00143 3 00217 1 00...

Page 71: ...MV DN 10 v 1 m s 3 ft s 0 4 of MV 1 mm s 0 4 of MV 0 04 inch s 0 2 of MV 1 mm s 0 2 of MV 0 04 inch s B D A E Current output same error limits as above additionally 10 A Reproducibility and repeatabi...

Page 72: ...iable Forward reverse flow measurment direction identified via status output Pulse output Function all operating data settable galvanically isolated from current output and all input circuits digital...

Page 73: ...e g hecto liters or US gallons day adjustable count duration up to overflow Language of plain texts English German French others on request Display Top field 8 character 7 segment numeral and sign dis...

Page 74: ...m oxide 99 7 Al2O3 H Hard rubber NE Neoprene PFA Teflon PFA PUI Irethane T Teflon PTFE W Soft rubber ZR Zirconium oxide Electrode material C conductive rubber compound HB 2 Hastelloy B2 HC 4 Hastelloy...

Page 75: ...rts 2 Since the magnetic field passes through the entire flow area the signal represents a mean value over the pipe cross section therefore only relatively short straight inlet pipes 5 x DN from the e...

Page 76: ...output signal from the P 3 microprocessor into a proportional current 4 Binary outputs and or inputs galvanically isolated from other groups selectable input output combinations pulse output B1 passi...

Page 77: ...2 4 4 5 4 1 04 Limit message 4 4 5 8 1 07 Line voltage see power supply Low flow cutoff SMU 4 4 5 3 1 03 Keyword Section No Fct No A Abbreviations 1 3 2 1 3 4 2 1 4 4 Accuracies 10 3 ADC analog digita...

Page 78: ...4 5 13 Measuring principle 11 Menu 4 1 4 4 Meter size DN 4 4 5 12 3 02 N Numerical format display 5 4 5 5 1 04 O Option optional equipment 6 2 10 4 Order numbers 9 Outputs characteristics 5 15 connec...

Page 79: ...meter is safe to handle If the flowmeter has been operated with toxic caustic flammable or water endangering liquids you are kindly requested to check and ensure if necessary by rinsing or neutraliz i...

Reviews: