3
TECHNICAL DATA
3.1
ASSORTMENT
Model
PRX3
Output data
Input data
Power
loss**
Rect. module Cubicle/weight
U
NOM
U
MAX
* I
RATED
Output
power
Terminal Mains
power*
Mains
current*
Mains
fuse
Terminal
Number I
RATED
F27 F41 S39
V
DC
V
DC
A
kW
mm
2
kVA
A
rms
A
gL/gG
mm
2
kW
A
kg kg kg
110/70
110 145
70
9
50
10.6
18
25
16
0.7
1
70
90 90 190
110/140
140
18
95
21.2
36
50
16
1.4
2
110 110 210
110/210
210
27
150
31.8
54
63
35
2.2
3
- 130 230
110/280
280
36
240
42.4
72
80
35
2.9
4
-
- 250
110/350
350
45
2x150 53.0
90
100
50
3.6
5
-
- 270
110/420
420
54
2x240 63.6
108
125
95
4.3
6
-
- 290
220/36
220 270
36
9
35
10.6
18
25
16
0.7
1
36
90 90 190
220/72
72
18
50
21.2
36
50
16
1.4
2
110 110 210
220/108
108
27
95
31.8
54
63
35
2.2
3
- 130 230
220/144
144
36
95
42.4
72
80
35
2.9
4
-
- 250
220/180
180
45
2x150 53.0
90
100
50
3.6
5
-
- 270
220/216
216
54
2x150 63.6
108
125
95
4.3
6
-
- 290
440/18
440 500
18
9
35
10.6
18
25
16
0.7
1
18
90 90 190
440/36
36
18
35
21.2
36
50
16
1.4
2
110 110 210
440/54
54
27
50
31.8
54
63
35
2.2
3
- 130 230
440/72
72
36
50
42.4
72
80
35
2.9
4
-
- 250
440/90
90
45
50
53.0
90
100
50
3.6
5
-
- 270
440/108
108
54
95
63.6
108
125
95
4.3
6
-
- 290
* maximum at 3x340 V
AC
** type at 3x400 V
AC
and full load
3.2
Electrical data
3.2.1
Electrical input data
Rated voltage .................................................. 380/400 V
AC
3-phase, TN network
Input voltage range ....................................... 340-440 V
AC
Overvoltage protection ................................ > 580 V
AC
, rectifier module stops
Undervoltage protection .............................. < 300 V
AC
, rectifier module stops
Frequency ........................................................ 45 – 65 Hz
Power factor.................................................... > 0.97 (at 3x400 V
AC
, full load)
Other, see table in section 3.1
3.2.2
Electrical output data
Voltage regulation (static) ........................... <±0.5 % of nominal output voltage
Voltage regulation (dynamic) ..................... <±1 % within 3 sec, 0-100 / 100-10 % load change
Current regulation......................................... <±1 % of rated current
Setting range, current limit.......................... 0 – 100 % of rated current
Ripple voltage ................................................ <0.2 %
RMS