5.2.3.1
AC OK
AC OK will be put on with green light if the mains supply is OK.
All indications put out, AC OK included, indicates that there is no mains
supply.
AC OK put out while the ALARM-led is red indicates that there is mains supply but not within
limits. The DC output is dead. See also section 4.2.10.
5.2.3.2
DC OK
DC OK will be put on with green light if the DC output is OK.
DC OK will be put out if the output voltage is below 50% of
nominal voltage. This means that it is also put out in normal standby state.
5.2.3.3
ALARM
The ALARM-led is put out in normal operation.
Red light indicates a fault condition. Also
standby state will give red light, because by the
systems point of view it is considered as a fault
condition.
The cause of the alarm can be studied in detail using the monitoring unit menu system, see
Manual for monitoring unit PCM2
.
5.2.3.4
CURRENT
The output current of the rectifier module, 0-100%, is shown by
a led-bar equipped with 10 yellow led-lamps. I.e. there are one
led for each 10:th percent of the rated current.