Switch on the AC input power MCB, then the DC output MCB.
The module is now ready to be started by using the buttons on the front panel.
9.4.2
Enclosure type S39
Begin with turning off the AC input power for the module by switching off the corresponding
MCB (F11 for module T1, F12 for module T2, etc.)
Also turn off the DC output power for the module by switching off the corresponding MCB
(F31 for module T1, F32 for module T2, etc.)
Pull out all cable sets from the rear of the module.
Loosen the four screws on the short sides of the
front of the module and pull out the module.
Push in the new module and fasten it by restoring
the four screws.
Connect the cable sets as they where before.
Switch on the AC input power MCB, then the DC output MCB.
The module is now ready to be started by using the buttons on the front panel.