Kozy-World GSN2821 Owner'S Operation & Installation Manual Download Page 5

                                    5

       WARNING:   Rework   worksheet,  adding   the  space  of   the  adjoining  unconfined  space.  The  combined
spaces  must   have  enough  fresh air  to supply  all  appliances  in  both  spaces.

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                    Btu/Hr
     Gas furnace                                                             Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                          Btu/Hr (maximum the space can support)
                         Btu/Hr (actual amount of Btu/Hr used)
         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building

, below.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

, below .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
 Vent-free  heater    +      26,000        Btu/Hr
 Total                         =     56,000        Btu/Hr

         WARNING:  If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as  an  unconfined
space or  if  the building  is  of  unusually  tight  construction, provide  adequate  combustion  and  ventilation air by  one

of   the  methods  described  in  the  National Fuel  Gas  Code, ANS  Z223.1, Section  5.3  or  applicable  local  codes.

This  fresh air  would come  from an adjoining  unconfined
space.  When  ventilating  to  an  adjoining unconfined
space, you  must  provide  two  permanent  openings: one
within 12

"

 of  the  ceiling  and  one  within 12

"

 of  the  floor

on  the  wall  connecting  the  two  spaces (see  options 1
and  2, Figure 2). You  can  also  remove  door  into
adjoining  room (see  option 3, Figure 2). Follow  the
National  Fuel  Gas  Code. NFPA  24/ANS  Z223.1.
Section 5.3,  Air  for  Combustion  and  Ventilation  for
required size of  ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors
Provide extra fresh air by using ventilation grills or ducts.
You must provide two permanent openings: one within
12

"

 of the ceiling and one within 12

"

 of the floor. Connect

these items directly to the outdoors or spaces open to the
outdoors. These spaces include attics and crawl spaces.
Follow the National Fuel Gas Code, NFPA 54/ANS
Z223.1, Section 5.3. Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for  inlet or outlet
air into attic if attic has a thermostat-controlled power
vent. Heated air entering the attic will activate the power
vent.

Figure  3 -Ventilation  Air  from  Outdoors

Summary of Contents for GSN2821

Page 1: ......

Page 2: ...mbustible materials gasoline and other flammable vapors and liquids 1 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with o...

Page 3: ...69 This heater is designed for vent free operation State and local codes in some areas prohibit the use of vent free heaters UNPACKING 1 Remove top inner pack 2 Tilt carton so that stove is upright 3...

Page 4: ...You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms wi...

Page 5: ...room unconfined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be...

Page 6: ...the minimum clearances If you can provide greater clearances from floor ceiling and adjoining side and back walls CAUTION This heater creates warm air currents These currents move heat to wall surfac...

Page 7: ...l gas models INSTALLATION ITEMS NEEDED Before installing heater make sure you have the items listed below l piping check local codes l sealant resistant to propane LP gas l equipment shutoff valve l t...

Page 8: ......

Page 9: ......

Page 10: ...l o w e r a s s e m b l y temporarily on top panel 12 Install control knob onto output shaft of operation control housing see figure 16 Place operation control housing just inside control compartment...

Page 11: ......

Page 12: ......

Page 13: ...er Maximum 14 Minimum 11 NG Manifold Pressure 3 0 W C Inlet Gas Pressure In of water Maximum 10 5 Minimum 5 Dimensions Inches H W D Stove 27 1 2 27 7 8 17 1 2 Carton 21 3 4 30 1 16 31 1 2 Weight pound...

Page 14: ...gas company B Clean ODS pilot see Cleaning and Maintenance or replace ODS pilot assembly 6 Replace thermocouple 7 Replace control valve POSSIBLECAUSE 1 Ignitor electrode positioned wrong 2 Ignitor ele...

Page 15: ...flame holes blocked 1 When heated vapors from furniture polish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance or replace burner orifi...

Page 16: ...ions page 8 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections page 8 1 This is common with most heaters If noise is...

Page 17: ......

Page 18: ...1 2 5 4 5 T I S e v l a V l o r t n o C t a t s o m r e h T 1 8 0 0 0 2 5 4 5 T I S e v l a V l o r t n o C t a t s o m r e h T 1 9 0 0 0 1 3 3 B S y l b m e s s A e b u T t e l t u O 1 0 1 2 0 3 8 0...

Page 19: ...1 9 ILLUSTRATED PARTS BREAKDOWN GSN2821 GSP2822...

Page 20: ...b e r i F 1 8 0 1 0 4 1 0 L S r o t c e l f e D t a e H 1 9 0 1 0 5 6 0 L S w e r c S g n i p p a t f l e S 4 0 1 1 0 8 0 0 L S r o o l F x o b e r i F 1 1 1 1 0 4 0 0 L S l e n a P t n o r F r e w o...

Page 21: ...e drawings to put log sets in place to the gas pedestal stove indoor vent free NOTICE THE POSITION OF THE LOGS SHOULD AVOID FLAME 1 Take out the paper liner See DRAWING 1 2 Take away the screen from t...

Page 22: ...2 2...

Page 23: ...of log B See Figure 3 3 Place the upper part of log D on the flat roof at the left side of log A Insert the pinhole on the lower part of log D into the pin on log C See Figure 4 4 Insert the pinhole o...

Reviews: