Kozy-World GSN2221 Owner'S Operation And Installation Manual Download Page 5

5

       WARNING:   

Rework   worksheet,  adding

the  space  of   the  adjoining  unconfined
space.  The  combined   spaces  must   have
enough  fresh air  to supply  all  appliances  in
both  spaces.

If  the actual  Btu/Hr  used  is   less  than   the  maximum   Btu/Hr   the  space  can  support, the   space  is   an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                    Btu/Hr
     Gas furnace                                                             Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                          

Btu/Hr (maximum the space can support)

                         

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building

.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

 .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
 Vent-free  heater    +      26,000        Btu/Hr
 Total                         =     56,000        Btu/Hr

         WARNING:  

If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as  an  unconfined

space or  if  the building  is  of  unusually  tight  construction, provide  adequate  combustion  and  ventilation air by  one
of   the  methods  described  in  the  

National Fuel  Gas  Code, ANS  Z223.1, Section  5.3 

 or  applicable  local  codes.

This  fresh air  would come  from an adjoining  unconfined
space.  When  ventilating  to  an  adjoining unconfined
space, you  must  provide  two  permanent  openings: one
within 12

"

 of  the  ceiling  and  one  within 12

"

 of  the  floor

on  the  wall  connecting  the  two  spaces (see  options 1
and   2, Figure 2). You  can  also   remove  door   into
adjoining  room (see  option 3, Figure 2). Follow   the

National  Fuel  Gas  Code. NFPA  54/ANS  Z223.1,  Sec-
tion 5.3,  Air  for  Combustion  and  Ventilation

  for required

size of  ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or ducts.
You must provide two permanent openings: one within
12

"

 of the ceiling and one within 12

"

 of the floor. Connect

these items directly to the outdoors or spaces open to
the  outdoors. These  spaces include  attics and crawl
spaces. Follow the 

National Fuel Gas Code, NFPA 54/

ANS Z223.1, Section 5.3, Air for Combustion and Venti-
lation

 for required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for  inlet or outlet

air into attic if attic has a thermostat-controlled power vent.
Heated air entering the attic will activate the power vent.

Figure  3 -Ventilation  Air  from  Outdoors

outlet

Summary of Contents for GSN2221

Page 1: ...n these instruction for future use WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be...

Page 2: ...nning heater Keep the appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids 1 This appliance is only for use with the type of gas indicated on the ra...

Page 3: ...m heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYS TEM This heater has a piezo ignitor This system requires no matches batteries or other sources to light...

Page 4: ...ATER LOCATION Determining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater...

Page 5: ...fined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be operated is...

Page 6: ...ter for proper type heater Figure 4 Minimum Clearance to Wall and Ceiling NOTICE This heater is intended for use as supplemental heat Use this heater along with your primary heating system Do not inst...

Page 7: ...make sure you have the items listed below l piping check local codes l sealant resistant to propane LP gas l equipment shutoff valve l test gauge connection l sediment trap l tee joint l pipe wrench l...

Page 8: ...controls If sediment trap is not installed or is installed incorrectly heater may not run properly CAUTION Avoid damage to regulator Hold gas regulator with wrench when connecting into gas piping and...

Page 9: ...structed Do not modify logs Only use logs supplied with heater IMPORTANT Make sure log does not cover any burner ports see Fig ure 10 Also see log placing instructions Figure 10 Installing Log Set Top...

Page 10: ...rom the fan to the Black Wire from the Switch Box and the other Black Wire to the White Wire Make sure these wires are clear of the fan Reattach the Back Panel using the 6 screws removed earlier Attac...

Page 11: ...1 1 Installing Blower Accessory BLOWER ACCESSORY 20 6028 OR 20 6029 Figure 15 F Mounting Blower And Installing Blower Control Housing Figure 14 F Routing Power Cord...

Page 12: ...12 column 1 If you don t smell gas go to the next step 6 Turn control knob counterclock wise to the PIILOT position Press in control knob for five 5 seconds see Figure 17 l Note You may be running thi...

Page 13: ...an burning flame Keep these holes clear of dust dirt lint and pet hair Clean these air inlet holes prior to each heating season Blocked air holes will create soot We recommend that you clean the unit...

Page 14: ...e 74 lbs Shipping 83 lbs For purposes of input adjustment CABINET Air Passageways l Use a vacuum cleaner or pressurized air to clean Exterior l Use a soft cloth dampened with a mild soap and water mix...

Page 15: ...lot see Cleaning and Maintenance or replace ODS pilot assembly 7 Replace thermocouple 8 Replace control valve POSSIBLECAUSE 1 Ignitor electrode is positioned wrong 2 Ignitor electrode is broken 3 Igni...

Page 16: ...or partially clogged burner orifice 1 When heated vapors from furniture polish wax carpet cleaners etc turn into a white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance or r...

Page 17: ...LP gas company 3 Clean ODS pilot 1 Locate and correct all leaks s e e C h e c k i n g G a s Connections 2 Replace control valve 1 Take apart the gas tubing and remove the foreign matter 2 Locate and...

Page 18: ...2222 GSN2221 K E Y N O PA R T NO D E S C R IP TIO N Q TY N G Q TY LP G S N 3011 G S N 2221 G S N 3013 G S P 3012 G S P 2222 G S P 3014 1 Q L019 01 Le g 1 1 Q L019 02 Le g 1 1 Q L019 01B Le g 1 Q L019...

Page 19: ...3 GSP3012 GSP2222 GSP3014 1 BL037 02 Log set 1 1 1 1 1 1 2 BL038 02 Log set 1 1 1 1 1 1 3 BL039 02 Log set 1 1 1 1 1 1 4 BL040 02 Log set 1 1 1 1 1 1 5 BL041 02 Log set 1 1 1 1 1 1 6 ND1703X400X4 ODS...

Reviews: