Kozy-World FBD2810T Manual Download Page 8

8

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space

: Includes the room in which you will install heater plus any adjoining rooms with door-less passageways or ventilation 

grills between the rooms.

1. Determine the volume of the space Length × Width × Height = cu. ft. (volume of space)

Example: Space size 20 ft. (length) × 16 ft.(width) × 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume 

of the space.

2. Divide the space volume by 50 cu. ft. to determine the maximum BTU/hr the space can support.

_______ (volume of space) ÷ 50 cu. ft.= (Maximum BTU/hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum BTU/hr the space can support)

3. Add the BTU/hr of all fuel burning appliances in the space.

Vent-free heater ________ BTU/hr

Gas water heater* _______BTU/hr

Gas furnace ___________ BTU/hr

Vented gas heater _______BTU/hr 

 

 

Example:

Gas heater logs ________ BTU/hr 

 

 

Gas water heater 30,000 BTU/hr

Other gas appl ___BTU/hr 

 

 

Vent-free 26,000 BTU/hr

Total =________________ BTU/hr 

   

    Total =56,000 BTU/hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4. Compare the maximum BTU/hr the space can support with the actual amount of BTU/hr used.

_______ BTU/hr (maximum the space can support)

_______ BTU/hr (actual amount of BTU/hr used).

Example : 51,200 BTU/hr (maximum the space can support)

 

56,000 BTU/hr (actual amount of BTU/hr used)

The space in the above example is a confined space because the actual BTU/hr used is more than the maximum BTU/hr the 

space can support.

You must provide additional fresh air. Your options are as follows:

a) Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to 

    adjoining room or add ventilation grills between rooms. See “Ventilation Air From Inside Building,” page 9.

b) Vent room directly to the outdoors. See “Ventilation Air From Outdoors”, Page 9.

c) Install a lower BTU/hr heater if lower BTU/hr size makes room unconfined. If the actual BTU/hr used is less than the 

    maximum BTU/hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Summary of Contents for FBD2810T

Page 1: ...his manual with the appliance CONSUMER Retain this manual for future reference WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE...

Page 2: ...arting installation Failure to follow these instructions may result in a possible fire hazard and will void the warranty PRODUCT SPECIFICATIONS Model FBD28T VENT FREE GAS FIREPLACE INSERT Input Rating...

Page 3: ...sory not approved for use with this heater Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Do not place clothing or other flammable materi...

Page 4: ...d items can cause sooting Do not add lava rock around base Rock and debris could fall into the control area of heater After servicing always replace screen before operating heater 16 This heater is de...

Page 5: ...sed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale...

Page 6: ...of water for every 1 000 BTUs 3 kw of gas input per hour An unvented room heater is recommended as a supplemental heater a room rather than a primary heat source an entire house In most supplemental...

Page 7: ...art of the unconfined space This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air Adjoining...

Page 8: ...ter logs ________ BTU hr Gas water heater 30 000 BTU hr Other gas appliances ___BTU hr Vent free heater 26 000 BTU hr Total ________________ BTU hr Total 56 000 BTU hr Do not include direct vent gas a...

Page 9: ...ing to an adjoining unconfined space you must provide two permanent openings one within 12 inches of the wall connecting the two spaces see options 1 and 2 Fig 2 You can also remove door into adjoinin...

Page 10: ...tc in the air exist may cause walls to discolor WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoining side and back walls IMPORTANT Vent free h...

Page 11: ...ons shown in Fig 8 for the rough opening The height is 26 1 2 in which is the same as the wall opening above 2 Carefully set fireplace in front of rough opening with back of fireplace inside wall open...

Page 12: ...ombustible materials to cover any necessary openings like louvered slots WARNING Never modify or cover the louvered slots on the front of the firebox Step 1 Step 3 Step 2 Fig 9 Remove two screws on to...

Page 13: ...cceptable alternative to test gauge connection Purchase the optional CSA design certified equipment shutoff valve from your dealer WARNING Never connect heater to private non utility gas wells This ga...

Page 14: ...end that you install a sediment trap in a supply line as shown in Fig 12 Locate sediment trap where it is within reach for cleaning and not likely to freeze Install in the piping system between fuel s...

Page 15: ...rter and turn knob clockwise until the knob locks into the NG position see Fig 14 3 Rotate and close cover over fuel selection device and reinstall screw 4 Remove steel or metal hex plug with wrench p...

Page 16: ...eater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig 16 2 Pressure supply...

Page 17: ...ns in this manual Flames contacting logs will create soot Fig 18 Installing Log Set IMPORTANT Make sure log does not cover any burner ports see Fig 18 It is very important to install the logs exactly...

Page 18: ...ap and install a AAA battery with the pointing out Replace cap 1 STOP Read the safety information on page 18 2 Warning You must operate this heater with the screen in place Make sure screen is install...

Page 19: ...ote The thermostat sensing bulb measures the temperature depending on housing construction TO TURN OFF GAS TO APPLIANCE Shut off heater Turn Control Knob clockwise to the OFF position Do not force MAN...

Page 20: ...ame Pattern Fig 22 Correct Pilot Flame Pattern with Control Knob Set to High Flame 5 Fig 23 Incorrect Pilot Flame Pattern with Control Knob Set to High Flame 5 Fig 21 Incorrect Pilot Flame Pattern BUR...

Page 21: ...pet hair etc The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clean burning flame Keep these holes clear of dust dirt and lint Clean these air inlet hole...

Page 22: ...Depleted gas supply 1 Turn on gas supply or open equipment shutoff valve 2 Fully press in control knob while pressing ignitor button 3 Continue holding down control knob for 30 seconds to remove air R...

Page 23: ...ct qualified service technician White powder residue forming within burner box or on adjacent walls or furniture 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white...

Page 24: ...ZY WORLD PHONE NUMBER 800 776 9425 When contacting your dealer have ready Your name Your address Model and serial numbers of your heater How heater was malfunctioning Type of gas used natural or propa...

Page 25: ...B 10 Fuel Selection Device Assembly YDF06 FBD28T 11 Hood FB28D04 B 12 Logs Set FB28D500 C 13 Log 1 FB28D501 C 14 Log 2 BL037 02 B 15 Log 3 BL038 02 B 16 Log 4 BL041 02 17 Log 5 FB28D505 C 18 Screen F...

Reviews: