26
VENTING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#SLA-60 R.8 March 2022
7.5 Vertical Terminations
IMPORTANT: The vertical vent heat shield must be installed for every
type of venting application. Refer to 7.8 on page 30.
NOTE: Attic insulation shields may be insulated using unfaced
insulation products listed as non-combustible per ASTM E 136.
Table 7.1, NG & Propane - Minimum / Maximum Vertical Terminations
Minimum Vertical Length
Maximum Vertical Length
3 ft
914 mm
50 ft
15.2 m
Minimum/ Maximum Vertical Venting:
3’ (914mm) minimum vertical length / 50’ (15.24m) maximum vertical
termination cap
DIAG.1 NATURAL GAS AND PROPANE VERTICAL VENTING
(A)
Stand-off Brackets
(B)
Stand-off Heat Shields
(C)
90
°
Elbow (not applicable)
(D)
Vertical Vent Heat Shield
(E)
Horizontal Vent Heat Shield (not
applicable)
(F)
Termination Cap