OPERATING INSTRUCTIONS 

27

11.1  Setup Proflame 2 IFC Module

1.  Locate the control module access switch on the left side of the 

fireplace.

2.  Set the main ON/OFF rocker switch in the OFF position.
3.  Install (3) AAA batteries (included in the components packet) in 

the remote control battery bay, located at the base of the remote.

4.  Connect the IFC Module to an AC power supply.

11.2  Initialize the Control System

IMPORTANT: Remove all packaging and combustible material from the 
firebox before initializing the control system.
NOTE: Performing the next steps will initiate pilot start-up in manual 
mode, where the pilot igniter will spark repeatedly. The pilot will ignite 
if gas is supplied to the fireplace. 

1.  Locate the remote sync button on the control module access 

switch on the left side of the fireplace.

2.  Press the remote sync button. The IFC module will BEEP (3) times 

and illuminate an amber LED. This indicates the receiver is ready 
to synchronize with the transmitter.

3.  Within (5) seconds, push the ON/OFF button on the remote 

control. The receiver will BEEP (4) times to indicate the transmitter’s 
command is accepted, and is set to the transmitter’s particular 
code. The pilot will automatically ignite. 

4.  Press the remote control ON/OFF button again. The pilot will 

extinguish, confirming the remote control command. The control 
system is now initialized. 

5.  Set the main ON/OFF rocker switch to ON position for remote 

control operation of the main burner and fireplace features.

11.3  Reset the System for 

Manual Operation

1.  Set the ON/OFF rocker switch to OFF position. 
2.  Press the remote sync button on the IFC module until it emits (3) 

beeps and an amber LED is illuminated. 

3.  Within (5) seconds, press the remote sync button again. This 

will close synchronization with the remote control. The pilot will 
automatically light. 

• 

Turn the main burner ON by setting the ON/OFF switch in ON 
position. The main burner will only operate on HI. 

• 

Turn the main burner OFF by setting the ON/OFF switch in the 
OFF position. The pilot will remain lit even if burner is turned off, 
provided CPI mode is turned on. 

11.4  Automatic Safety Restart

• 

This system will execute an automatic turn OFF command for 
approximately (5) seconds within (24) hours of a continued pilot 
flame ignition to perform a safety check. This allows the system to 
verify correct safety functions. 

• 

After the turn OFF sequence is completed, the IFC module will re-
execute the latest command. 

11.5  Backup Battery Operation 

This electronic ignition system utilizes the supplied 110 VAC power 
when it is available for all functions of this system. If the AC power is 
interrupted during a power outage, plug in the battery pack (9V DC 
max, supplied with this fireplace) to the backup 9V DC power jack. 
During the power outage, the appliance burner and flame height 
adjustment will function. The fan and accent light kit will not function. 
See the figure below on how to plug in the battery backup into the 
inlet port.

POWER SWITCH

REMOTE SYNC BUTTON

BACKUP 9V DC POWER JACK

Figure 11.1, Control module access switch

Figure 11.2, Backup Battery and Inlet Port

Summary of Contents for ROOSEVELT 29 BW

Page 1: ...manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for u...

Page 2: ......

Page 3: ...being dedicated not only to functionality and reliability but also customer safety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat...

Page 4: ......

Page 5: ...ace and Secure Appliance 17 7 0 GAS LINE CONNECTION 18 7 1 Gas Conversion sold separately 18 7 2 Gas Line Installation 18 8 0 FACING AND FINISHING 19 8 1 Clearances to Combustibles 19 8 2 Shroud Insta...

Page 6: ......

Page 7: ...y period a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above pr...

Page 8: ...e installed at higher altitudes Please refer to National Fuel Gas Code ANSI Z223 1 NFPA 54 CSA B149 1 Natural Gas and Propane Installation Code local authorities or codes having jurisdiction in you ar...

Page 9: ...TIONS 9 2 2 Appliance Dimensions Figure 2 1 Appliance Dimensions 201 16 510mm 16 406mm 2711 16 703mm 295 8 753mm 197 8 505mm 1715 16 456mm 13 16 31mm 14 356mm 6 172mm 11 8 28mm 129 16 319mm 33 16 81mm...

Page 10: ...roved parts with this appliance may result in property damage or personal injury Figure 2 2 Proper Positioning of Appliance Table 2 1 Field Assembled Parts A Fireplace insert G Burner air flow plate B...

Page 11: ...th Hussong Mfg s barriers for this appliance Only doors certified with the appliance shall be used IMPORTANT Consider the height of hearth finish material when building a fireplace platform Proper ins...

Page 12: ...D label at bottom of existing firebox so it will be visible if this gas fireplace insert is removed 3 2 1 1 Existing Fireplace Opening Minimum Requirements If installing the RT29 FLP add 3 4 19mm tota...

Page 13: ...1 Vent Termination Clearances WARNING This appliance must not share or be connected to a chimney flue serving any other appliance Approved vent caps require 12 in 305mm clearance to intersecting wall...

Page 14: ...ce has no gas access hole s provided an access hole of 1 in 37 5 mm or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner The access hole must be...

Page 15: ...y cause abrasion or damage to the flexible pipes 1 Measure the total chimney length required and cut 816 36 10 97m of 3 flexible pipe to the measured length 2 Carefully extend the exhaust and combusti...

Page 16: ...through the chimney place unfaced insulation around the first 3 ft 914 mm of vent system below termination cap Secure with wire 2 Install the 3 x 3 flexible pipes down through existing chimney Guide...

Page 17: ...appliance is properly positioned Figure 6 4 Aligned Insert 6 5 Connect Vent Pipe to Vent Adapter IMPORTANT Proper operation of this insert requires the exhaust pipe and combustion air pipe to be conne...

Page 18: ...m tee handle manual shut off valve and flexible gas connector are to be connected to the in 13 mm control valve inlet If substituting for these components please consult local codes for compliance If...

Page 19: ...Clearances to Combustibles IMPORTANT Adequate accessibility clearances for servicing and proper operation must be maintained COMBUSTIBLE MATERIAL 4 102mm 12 305mm 9 229mm 11 286mm 8 210mm 281 8 714mm...

Page 20: ...Align leg section holes on the shroud to the corresponding mounting nuts in mounting brackets on each side of the insert metal cabinet 3 Secure with 4 phillips truss head screws provided 4 Reinstall...

Page 21: ...s assembly into position 2 Using the glass latch tool pull latches out and down over latch tabs to secure glass frame assembly bottom 9 2 Light Kit CAUTION Disconnect all electrical power from the fir...

Page 22: ...along the front of the plate positions at the bottom of the firebox Tilt the bottom of the plate in first The plates will install along the side of the burner and sit on the firebox floor 2 Install t...

Page 23: ...nversion before installing the log set Follow the conversion instructions included with the kit Log numbers located on the bottom of each log Refer to following instructions and illustrations for prop...

Page 24: ...ol board on the left side of the firebox 12 Pull out control board out to reveal gas line to disconnect the gas line flex tube from fireplace valve 9 5 2 Control Board Installation 1 Place control boa...

Page 25: ...ceptacle Do not cut or remove the grounding prong from this plug 10 1 Electrical Specifications This appliance when installed must be electrically grounded in accordance with local codes or in the abs...

Page 26: ...an ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Locate the manual valve installed by your qualified service technician 6 Turn the manual valve clockwis...

Page 27: ...control operation of the main burner and fireplace features 11 3 Reset the System for Manual Operation 1 Set the ON OFF rocker switch to OFF position 2 Press the remote sync button on the IFC module u...

Page 28: ...h to the OFF position 2 After approximately 2 seconds move the switch to the ON position The ignition sequence will start again 11 6 1 2 Remote Control ON OFF Key 1 Press the remote control ON OFF key...

Page 29: ...ark to pilot system to the standing pilot option The standing pilot will keep the firebox warm and establish a draft in the vent which allows the main burner to ignite with less air flow disruption Wh...

Page 30: ...off key and the mode key at the same time 4 Reinsert 1 AAA battery 5 While still holding the on off key let go of ONLY the mode key 6 Index over to the flame graphic on the LCD screen to edit Use the...

Page 31: ...replace before fan operation The fan will continue to operate for approximately 12 minutes after the fireplace has been turned off Manual mode Fan s will operate at previous setting There is no delay...

Page 32: ...mum and maximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten 6...

Page 33: ...3 Factory Set Venturi Openings Fuel FRONT BACK Natural Gas 1 16 1 5 mm OPEN 1 16 1 5 mm OPEN Propane 3 8 9 5 mm OPEN 3 8 9 5 mm OPEN 12 2 1 1 Venturi Adjustment NOTE If soot is present on the glass c...

Page 34: ...Do not over tighten Pilot flame always on or will not extinguish Control system set to CPI mode Set control system to IPI mode Main burner flame will not light ON OFF rocker switch in OFF position Swi...

Page 35: ...nturi setting Venturi air shutter may need to be opened slightly to allow more air into the gas mix Refer to section 12 2 1 Burner Venturi on page 33 Incorrect vent cap installation Adjust if necessar...

Page 36: ...uctions provided with installation Refer to Section 6 0 on page 15 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required The flow of combustion and...

Page 37: ...ion device Visually check pilot light when in operation Inspect and ensure the lighting of the main burner occurs within 4 seconds of the main gas valve opening Check for faulty or incorrect wiring an...

Page 38: ...T IPI Gas Valve Propane 700 567 1 Valve Step Motor Propane 700 504 1 Proflame 2 IFC Board 700 652 15 in Flexible Gas Line Black 700 227f IFC Wire Harness Assembly 700 653 Flexible Gas Line Valve to Bu...

Page 39: ...f but not limited to improper chimney venting installation will also render this warranty void 7 This warranty does not cover installation and operational related problems such as environmental condit...

Reviews: