#NDK-34-i R.1 July 2022
Hussong Mfg. Co., Inc. Kozy Heat Fireplaces
2
4
8.0
FACING AND FINISHING
8.1
Facing and Finishing Requirements
IMPORTANT: Adequate accessibility clearances for servicing and
proper operation must be maintained.
8.1.1
Adjacent Sidewall Requirements
•
The adjacent sidewall minimum clearance is 4” (1022mm) from
the appliance sides (Fig 8.1).
•
Minimum clearances to a combustible mantel leg is 1-1/2”
(38mm) (Fig. 8.2).
8.1.2
Clearance to Ceiling
•
As shown in Figure 8.1, the minimum clearance from the
fireplace enclosure floor to the ceiling is 55” (1.04m).
8.1.3
Mantel Requirements
WARNING: All minimum clearances to combustible material MUST be
maintained.
•
Combustible Mantel Projections: As referenced in Figure 8.4
(page 26) the optional 3/4” (19mm) trim can start at 6-1/2”
(165mm) above the top of the appliance with a 9” (229mm)
mantel starting at 10” (254mm) above the top of the appliance.
Mantel projections can increase 1” (25mm) of depth for every 1”
(25mm) of height starting at the 6” (152mm) mantel.
•
Non-combustible Mantel Projections: As referenced in Figure
8.4 (page 26). A minimum vertical clearance of 6” (152mm)
above the appliance to a maximum 6” (152mm) depth of a
non-combustible mantel. Follow projection 1” (25mm) up for
every 1” (25mm) deeper.
8.1.4
Hearth Requirements
Hearth can be made of combustible materials as long as it is in front of
the fireplace and flush or below the fireplace bottom
Figure 8.3, Hearth Requirements
Figure 8.1, Clearance to sidewall
Figure 8.2, Mantel Leg
FACING AND FINISHING