GAS LINE CONNECTION
Run gas line through left gas line access hole at back corners of insert. For your convenience, access hole may be removed and rotated to
accommodate side gas line installation.
This fireplace is manufactured for use with Natural Gas. An LP conversion kit is included with this fireplace.
Follow instructions included with conversion kit if converting to LP gas.
GAS CONVERSION
NATURAL GAS
LP GAS
MINIMUM INLET GAS PRESSURE
5” WC (1.25 kPa) (7” WC (1.74 kPa) recommended)
11” WC (2.74 kPa) (recommended)
MAXIMUM INLET GAS PRESSURE 10.5” WC (2.62 kPa)
13” WC (3.24 kPa)
MANIFOLD PRESSURE (HI)
3.5” WC (.87 kPa)
10.0” WC (2.49 kPa)
MANIFOLD PRESSURE (LO)
1.0” WC (.25 kPa)
2.8” WC (.67 kPa)
ORIFICE SIZES
#44 & #53
#54 & #61
INPUT BTU/hr.
32,000 (9.38 kW)
32,000 (9.38 kW)
MINIMUM INPUT BTU/hr.
16,500 (4.84 kW)
16,500 (4.84 kW)
The manual shut-off valve is located on left side wall of insert. Use glass
latch attachment tool (included in components packet) to open or close
valve.
MANUAL SHUT-OFF VALVE
SHOWN IN OPEN POSITION
NOTE
If installing this gas fireplace insert into a factory-built fireplace and the factory-built fireplace has no access hole provided, an
access hole of 1-1/2"(38mm) or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship
like manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed.
ATTENTION
The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in
accordance with the requirements of the ANSI Z223.1 installation code.
CAUTION
Installation of the gas line must only be done by a qualified person in accordance with local building codes, if any.
If not, follow ANSI 223.1.
Commonwealth of Massachusetts: Installation must be done by a licensed plumber of gas fitter.
NOTE
A listed (and Commonwealth of Massachusetts approved) 1/2” (13mm) T-handle manual shut-off valve and flexible gas
connector (included) are connected to the 1/2” (13mm) control valve inlet. If substituting for these components, please consult
local codes for compliance.
This fireplace is equipped with a 3/8”(10mm) x 18” (457mm) long flexible gas connector and manual shut-off valve. The gas
line should be run to the point of connection where the shut-off valve and flexible gas line will connect.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The appliance must be isolated from the gas supply piping
system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal
to or less that 1/2 psi (3.5 kPa).
For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper rating methods
.
IMPORTANT
The efficiency rating of this appliance is a product of thermal efficiency rating determined under continuous operating
conditions and was determined independently of any installed system.