13
6. Test inlet pressure, referring to page 29
For proper testing procedures. Chart
below states proper pressure readings.
7. Visually check pilot flame. Flame should envelope top of flame sensor and
extend onto burner far enough for proper ignition. To Adjust pilot: Turn pilot
adjustment screw clockwise to decrease or counter-clockwise to increase
pilot flame.
8. Turn fireplace off.
9. Affix gas type sticker to label.
10. Re-install glass frame and screen front assemblies.
11. Verify proper ignition and operation of fireplace. Refer to page 31 For proper
pilot and burner flame appearance and adjustment.
12. Complete and affix ‘Gas Conversion’ label to outer wrap as close to rating
plate as possible.
CONVERT THE GAS CONTROL VALVE:
1. Remove cap covering the pressure regulator .
2. Press down on pressure regulator tube and rotate 90
˚
. The shaft should pop
out and point to chosen gas. Re-attach cap.
3. Remove low limit screw (above valve motor; see page 20). Replace with one
included in kit. (Number stamped on low limit screws).
NAT GAS: #40 / LP GAS: #55
COMPLETE THE CONVERSION:
1. Adjust burner tube venturis to correct setting by loosening screws, adjusting
caps and retightening screws.
CORRECT SETTINGS: NAT: Both venturis - 1/16” (2mm) open
LP: Both venturis - 5/8” (16mm) open
2. Re-install front burner into fireplace, pull bracket forward until orifice is
properly seated inside burner venturi; tighten bracket nut.
3. Install back (top) burner. Burner venturi extends through center opening on
front (bottom) burner and sits down over back burner orifice. Ensure pilot
assembly sits above burner. Align holes in both burners and secure with
screws previously removed.
4. Re-install logs.
5.
Turn on gas and electrical supplies. Check for leaks at all connections with
soapy water, whether field or factory made.
CONVERSION KIT INSTRUCTIONS
GAS TYPE CONVERSION:
Press and hold Learn Button on Main Control Module for 20 seconds (access hole in center of module housing, located behind left
component access door). A beep will be heard letting you know the procedure has been completed.
If converting from NAT to LP gas:
one (1) second long beep
If converting from LP to Nat gas:
three (3) second long beep
L.P. SETTING
PRESSURE REGULATOR CAP
NAT. SETTING
Figure 13a
GAS CONVERSION LABEL
(included with conversion kit)
Figure 13c
PROPER BURNER / PILOT ASSEMBLY ORIENTATION
PILOT ASSEMBLY
BURNER ASSEMBLY
NATURAL GAS
LP GAS
MINIMUM INLET GAS PRESSURE
5” WC (1.25 kPa) (7” WC (1.74 kPa) recommended)
11” WC (2.74 kPa) (recommended)
MAXIMUM INLET GAS PRESSURE 10.5” WC (2.62 kPa)
13” WC (3.24 kPa)
MANIFOLD PRESSURE (HI)
3.5 (.87 kPa)
10.0 (2.49 kPa)
MANIFOLD PRESSURE (LO)
1.0 (.25 kPa)
2.8 (.67 kPa)
Figure 13b