Control System 7 Day Timeout–Additional Diagnostic Information
SECTION 10
OPERATING INSTRUCTIONS
65
#BHM-38 & #BHM-38-BW
R.1 September 2021
HUSSONG MFG. CO., INC.
KOZY HEAT FIREPLACES
10.6 Control System 7 Day Timeout
•
If you have your Proflame 2 system set to CPI (continuous pilot
ignition) with
7
consecutive days
without ignition of the main
burner, the pilot will turn off. This a standard safety feature of the
SIT Proflame 2 system.
•
Once you turn CPI on, the
7
day timer will start. If at any time
during the following
7
days your main burner ignites, it will reset
the timer back to
7
days.
•
See section
10.9.3 PILOT IGNITION SELECTION
(page 66) for
more information.
How to check if your system is set to CPI:
The LCD screen will display the snowflake icon.
To select the preferred pilot ignition feature,
1. With the system in the OFF position, press the mode key to index
the CPI mode icon.
2. Press the up arrow key to activate CPI.
3. Press the down arrow key to return to IPI. A single ‘beep’ will
confirm reception of the command.
To Turn ON the appliance:
1. With the system in the OFF position, press the remote control
ON/OFF key to turn ON the appliance.
A single ‘beep’ will emit from the IFC module to confirm recep-
tion of the command.
The LCD screen will display all active icons, and the IFC module will
start the ignition sequence.
10.7 IFC Module Ignition Sequence
The IFC module will try (2) times for ignition, each lasting
approximately (60) seconds, with approximately (35) seconds
between each attempt.
1. With the system in OFF position, press the remote control ON/OFF
key. Approximately (4) seconds after this key is depressed, the IFC
module will generate sparks to the pilot hood.
2. First ignition attempt will generate sparks for (60) seconds.
3. If there is no flame ignition (rectification) within the (60) second
time frame, the IFC module will stop generating sparks for
approximately (35) seconds.
4. After (35) seconds of wait time, the IFC module will generate
sparks for another (60) seconds for the second ignition attempt.
5. If there is no positive rectification after (60) seconds, the IFC
module will go into a lock out. The red LED will blink (3) times, in
intervals, until the system is reset.
10.7.1 Reset IFC Module after Lockout
10.7.1.1 ON/OFF Rocker Switch
1. Set the ON/OFF rocker switch to the OFF position.
2. After approximately (2) seconds, move the switch to the ON
position. The ignition sequence will start again.
10.7.1.2 Remote Control ON/OFF Key
1. Press the remote control ON/OFF key to turn the system OFF.
2. After approximately (2) seconds, press the ON/OFF key again. The
ignition sequence will start again.
10.7.1.3 Cycling Flame
1. Press the remote control down arrow key during flame adjustment
mode to reduce the flame to OFF (indicated by OFF displayed on
the LCD screen).
2. After approximately (2) seconds, press the up arrow key. The
ignition sequence will start again.
10.8 Additional Diagnostic Information
Low Battery Condition (<4V) Remote Control:
•
Battery Icon will appear on LCD remote control display.
•
Replace batteries.
Low Battery Condition (<4V) Battery Backup:
•
The red LED Indicator will blink (1) time in intervals.
•
A low double-beep emits from the IFC control module when it
receives an ON/OFF command from the remote control.
•
Replace Batteries.
Pilot Flame Error Condition:
•
Red LED Indicator will blink (2) times in intervals. Contact your
dealer if this occurs.
System Lock Out Condition:
•
Red LED Indicator will blink (3) times in intervals.
•
Verify gas is turned on.
•
Verify sensor is not shorted.
•
Follow section
10.2, INITIALIZE THE CONTROL SYSTEM
on
page 64.