Basic information by communication problems 

Experience has shown that switches or WLAN repeaters that do not support multicasting or do not 
properly process and distribute multicast packets (keywords: IPTV, network printer, IP camera, etc.) 
are often installed in the event of communication problems.  

It must therefore be ensured that the communication interfaces of the PV system are not disturbed in 
any way.  

If multicast filtering with Internet Group Message Protocol (IGMP*) is not used, the interfaces may be 
overloaded because they must respond permanently to multicast traffic that is not intended for them. 

Please note that KOSTAL cannot provide detailed recommendations for suitable network devices or 
support for the network architecture. 

If you are using a Telekom media receiver that is to be connected via WLAN, powerline or switch, you 
will find a list of working combinations in the official Telekom Helps Community: 

https://telekomhilft.telekom.de/t5/Fernsehen/EntertainTV-neu-Liste-funktionierender-Kombinationen-
mit-WLAN/td-p/1867188

 

Please consult your network specialist or provider if you need further assistance. 

*Note: The current IGMP version 3 is used e.g. for the provision of the IP-TV service "Entertain" of 
Deutsche Telekom. 

 

 

In addition, the following points must be observed to ensure interference-free and secure data 
transmission: 

1.  Signal, data and communication lines must be strictly separated from power cables. Pay 

attention to separators in cable ducts. 
 

2.  Only use cables and wires for data transmission that are approved and/or suitable for this 

purpose. 
 

3.  The inverter (additional grounding on the casing frame) and the battery (grounding of the 

BMS) must be at exactly the same ground potential. Determine the low resistance of the 
individual protective conductors by means of a measurement. Only if the battery and the 
inverter are properly grounded can trouble-free and reliable data transmission be guaranteed. 
 

Summary of Contents for BYD HV H11.5

Page 1: ...and installation The trademarks trade names product descriptions and other designations used may be protected by law even without special designation e g as trademarks KOSTAL Solar Electric GmbH does...

Page 2: ...or on the supply lines Refer to the relevant operating instructions for the respective devices inverter battery Install PLENTICORE plus inverter connect AC cables and control cables but DO NOT start u...

Page 3: ...NTICORE plus or PIKO IQ inverters The KOSTAL Smart Energy Meter can be installed directly in the sub distribution cabinet and connected to the inverter without a PC adjustment of parameters and other...

Page 4: ...BCU of the BYD Battery Box HV via WLAN Activating the WLAN on the computer Select the BYD battery from the list of devices in the WLAN network Enter the network key for the WIFI of the BYD battery acc...

Page 5: ...st be entered Then click on the Next button Series Battery Counts Enter number of memory modules 4 to 9 Inverter Select inverter manufacturer KOSTAL Country Select your country e g Germany Finally cli...

Page 6: ...he installation assistant appears in the inverter display Commissioning can be carried out completely via the display Simply follow the instructions on the display Alternatively the commissioning can...

Page 7: ...Seite 7 12 DOC_Guide_PLENTIOCRE_BYD_ 2019 04 17 FW_1 20_EN All other settings can now be entered in the service menu Service menu Energy management Choice of energy meter and position of the sensor...

Page 8: ...with the Energy Manager from B control the EM300 LR as well as with the KOSTAL Smart Energy Meter KSEM IMPORTANT The sensor Energy Manager Meter must be mounted in the Mains connection point position...

Page 9: ...Seite 9 12 DOC_Guide_PLENTIOCRE_BYD_ 2019 04 17 FW_1 20_EN Service menu Battery settings All settings for the connected battery made here...

Page 10: ...is available Download from our homepage Download and install the software for the PLENTICORE plus inverter that was released up to date at the time of installation This software can be downloaded fro...

Page 11: ...EC 5095 The inverter cannot measure the battery voltage at DC input 3 With this message no voltage is detected at the DC3 input of the WR from the battery Is the battery on the circuit breaker switch...

Page 12: ...h you will find a list of working combinations in the official Telekom Helps Community https telekomhilft telekom de t5 Fernsehen EntertainTV neu Liste funktionierender Kombinationen mit WLAN td p 186...

Reviews: