6
Configuration
Heating box size 15 kW
Heating box size 24 kW
Heating box size 27 kW
P
P
P
P
P
P
P
P
P
7
Before you supply voltage for the first time, make sure that
you set the heater’s power at appropriate value (always
consider the capacity of your home’s electrical system).
Notice: Configuration must be performed before initial
start-up when power supply is switched off. Set
2 (two) switches at proper position to configure
a heater. The switches are located on electronic
board. Each switch has 4 (four) positions, they
are described as
P
(power settings) and
F
(other
settings). Switch on a power supply to upgrade
configuration. After you supply power to PPE2 or PPVE
a display will show: (PW...) - software version of control
panel, (MSP...) - software version of controller and the
value of rated power that has been set for the heater
(PPE2; PPVE).
P
switches settings (for PPE2, KDE2, PPVE):
•
1, 2 - rated power of heater,
•
3, 4 - type of heating box,
Do not reset
P
switches for KDE - keep factory settings
intact.
F
switches settings:
•
1, 2, 3 - do not change! keep factory settings
intact,
•
4 - ON - blocks access to the heater’s settings.
In this case for PPE2 or PPVE, the display shows
the desired temperature value (which has been
adjusted before the heater is off), the heating icon
and other possible working characteristics.
Weight square shows the
switch position
The heater is factory set at NORMAL mode (30-60ºC). To use the heater for shower
purposes it has to be changed to SHOWER mode (30-55ºC). Change of the modes
can only be done by authorised service.
Venting
1. Shut off electric supplies to the heater
2. Turn the flow on (turn the hot water tap on) in order to vent the water installation
(for about 15-30 seconds), until the flow of water becomes constant and even.
3. Switch on the electric supplies.