2.2

 

Features 

 

1.

 

If  the  set  humidity  is  higher  than  the  ambient  humidity,  the  dehumidifier  will  enter  the  "wet 

control state" and will not run. 

2.

 

When entered  dehumidification  mode,  the  fan  is turned  on  for  5s  to start  the  compressor;  when 

the dehumidifier stops working, it will first turn off the compressor, then turn off the fan after 30s; 

3.

 

After the compressor is turned off, it takes 3 minutes to restart. When the compressor is running 

for 72 hours, the system will automatically resume after 30 minutes of forced stop. 

4.

 

When  running  at  a  lower  temperature,  the  machine  will  automatically  detect  the  system 

temperature. When reached the defrosting temperature, it will automatically stop and defrosting. The 
“snow  pattern”  will  light  up  and  the  “defrosting  pattern”  will  shine.  After  the  defrosting,  the 

dehumidifier starts automatically. 

5.

 

Humidity control operating range: 10%~90%. 

 

6.

 

If the dehumidifier is not used for a long time, remove the power cord or power off. 

 

7.

 

The function of the memory system, the function can function before the power is turned off in 72 

hours after the power is lost. (Note: When you leave the humidifier, please turn off the source) 

 
 

3.

 

Operating Instructions 

When the substrate is powered on for the first time, the substrate enters the standby state, press the 

power  button  and  set  the  required  humidity  3%  less  than  the  current  humidity  to  enter  the  running 

state, If the setting humidity is higher than ambient humidity, the dehumidifier will not work. 

 

3.1

 

Dehumidifying Running 

 

1.

 

When  the  compressor  has  passed  the  protection  for  3  minutes  and  the  indoor  humidity  ≥set 

hu3% RH, the compressor will work again. 

2.

 

When the indoor humidity <set humidity -2% RH, the compressor is turned off. 

 

3.

 

Set humidity -3%RH <indoor humidity <set hu3%RH to keep compressor working.

 

 

4.

 

The compressor stops the fan if it has not been operated 3 minutes after the humidity has dropped. 

 

5.

 

Defrost 

Summary of Contents for KM-480S

Page 1: ...Industrial Dehumidifier User Manual KM 480S www kosmen vn...

Page 2: ...1 2 Function of the Button 2 2 1 Operation 2 2 2 Features 4 3 Operating Instructions 4 3 1 Dehumidifying Running 4 3 2 Drain Indicator 5 4 Device Installation 5 5 Specification 7 6 Error Code Explana...

Page 3: ...b o quan tr ng 09 2 C c n t ch c n ng 10 2 1 V n h nh 10 2 2 Ch c n ng 12 3 H ng d n v n h nh 12 3 1 Ch y m y h t m 12 3 2 n b o tho t n c 13 4 C i t thi t b 14 5 Th ng s k thu t 15 6 Gi i th ch m l i...

Page 4: ...ke sure that it is not punctured or frayed Inspect the plug to ensure that the prongs are secure and the plastic surrounding it is not cracked Do not suddenly unplug the power plug while the machine i...

Page 5: ...2 2 Function of the Button 2 1 Operation...

Page 6: ...3...

Page 7: ...l operating range 10 90 6 If the dehumidifier is not used for a long time remove the power cord or power off 7 The function of the memory system the function can function before the power is turned of...

Page 8: ...the pipe from being too long or the pressure is formed in the pipe when the water outlet is blocked The water flow is not smooth resulting in water leakage Inspection and Maintenance Parts 1 3 months...

Page 9: ...fuse current of the power supply fuse is 1 5 to 2 times the rated current of the installed dehumidifier The fuse should be installed in the dehumidifier attachment The power supply cable and main fus...

Page 10: ...Drainage Dimensions 1030 510 1815 mm Net Weight 182 KGS 6 Error Code Explanation Fault Code The failure How to do with it E1 Temperature sensor breakdown To replace with new temperature sensor E2 Humi...

Page 11: ...iate 2 The front and back may be blocked 3 Dehumidification time isn t enough 4 Door and window may be open 5 Temperature 5 or 38 1 Set appropriate humidity 2 Clear the obstructions 3 Keep waiting 4 C...

Page 12: ...i m tra d y i n c n th n m b o r ng n kh ng b th ng ho c s n Ki m tra ph ch c m m b o c c u c m c ch c ch n v l p nh a bao quanh kh ng b n t Kh ng c r t ph ch c m i n t ng t khi m y ang v n h nh Tr c...

Page 13: ...10 2 C c n t ch c n ng 2 1 V n h nh...

Page 14: ...11...

Page 15: ...m so t m 10 90 6 N u m y h t m kh ng c s d ng trong m t th i gian d i h y r t d y ngu n ho c t t ngu n 7 H th ng c ch c n ng ghi nh ch c n ng n y c th ho t ng tr c khi t t ngu n trong v ng 72 gi sau...

Page 16: ...n c tr nh tr ng h p ng ng qu d i ho c t o p l c trong ng khi ng tho t n c b t c D ng n c ch y kh ng th ng su t d n n r r n c Ki m tra v B o tr C c b ph n 1 3 th ng 12 th ng M ng l c V sinh m ng l c M...

Page 17: ...p v t n s m thi t y u c u Vi c ki m tra n y c bi t quan tr ng i v i c c dao ng i n p c th x y ra trong c c t nh hu ng qu t i 3 M y h t m ph i c n i t v t c ng t c ng t i n m b o thi t b c t t ngu n tr...

Page 18: ...pply 380V 50Hz Operating Temp 5 38 Water Tank Drainage Dimensions 1030 510 1815 mm Net Weight 182 KGS 6 Gi i th ch m l i M l i L i H ng x l E1 S c c m bi n nhi t Thay c m bi n nhi t m i E2 S c c m bi...

Page 19: ...u ng h t m kh ng t y u c u 1 C i t m kh ng ph h p 2 M t tr c v m t sau c a m y h t m c th b c n tr 3 Th i gian h t m c th kh ng 4 C a ra v o v c a s ang m 5 Nhi t trong nh th p h n 5 ho c cao h n 38...

Page 20: ...iep Binh Phuoc Thu Duc City Ho Chi Minh City Vietnam Ha Noi office No 3 Lane 495 Nguyen Trai Thanh Xuan Nam Ward Thanh Xuan District Ha Noi City Vietnam Da Nang office No 385B Hai Phong Tan Chinh Ward...

Reviews: